Controller
Indication on the
Meaning
display
This value is only displayed if "YES" has been set in the
Replacement
"With softening" menu option.
18 months
Manufacturer specification for the replacement
interval of the softening cartridges, regardless of
the calculated soft water capacity. The system
displays the "Softening" message.
Next maintenance
Recommended maintenance messages.
012 months
Off: Without maintenance recommendation.
001 – 060: Maintenance recommendation in
months.
Floating fault
For the output of messages to the floating contact,
contact
 9.2.2 "Messages",  30.
YES
YES: Output of all messages.
NO: Output of all messages identified with "xxx"
("01", for example).
Switch to the "Fault memory" sub-menu.
Fault memory˃
Press "OK" to open the menu.
Use the "▼▲" buttons to open the sub-menu.
ER 01...xx
The last 20 alarms are stored with fault type, date, time,
and fault code.
See the chapter "Messages" for more information about
the ER... messages.
Parameter
Switch to the "Parameter memory" sub-menu.
memory˃
Press "OK" to open the menu.
Use the "▼▲" buttons to open the sub-menu.
P0 = xx.x bar
The last 10 entries of the minimum working pressure are
stored with date and time.
Date | Time
Vessel info
The system displays the values for the volume and the
diameter of the "RG" primary vessel.
00600 l
If you identify differences to the information
provided on the primary vessel's nameplate, please
contact the Reflex Customer Service.
Reflexomat
Information about the software version
V1.00
9.2.1
Default settings
The device controller is shipped with the following default settings. Use the
Customer menu to adjust these values to local conditions. In specific cases, it is
possible to further adjust the values in the Service menu.
Customer menu
Parameter
Setting
Language
DE
Minimum operating
1.8 bar
pressure "P
"
0
Next maintenance
12 months
Volt-free contact
YES
Make-up
Make-up "ON"
8 %
Make-up "OFF"
12 %
Maximum make-up
0 Litres
volume
Maximum make-up time
30 minutes
ER
Alarm
Code
01
Minimum pressure
YES
30 — English
Comment
Display language.
 7.2 "Reflexomat switching
points",  27.
Time left to the next due
maintenance.
 9.2.2 "Messages",  30.
Only if make-up has been
selected in the customer menu
with "With water meter Yes".
Floating
Causes
contact
Set value not reached.
Water loss in the system.
Compressor fault.
Controller in Manual mode.
Reflexomat Basic — 13.11.2020 - Rev. A
Parameter
Setting
Maximum make-up cycles 6 cycles within
2 hours
Softening (Only if "With
softening Yes")
Shut off make-up
No
Hardness reduction
8°dH
Maximum make-up
0 Litres
volume
Soft water capacity
0 Litres
Cartridge replacement
18 months
Service menu
Parameter
Setting
Pressurisation
Compressor "ON"
P
+ 0.3 bar
0
Compressor "OFF"
P
+ 0.4 bar
0
"Compressor run time
240 minutes
exceeded" message
Overflow line "CLOSED"
P
+ 0.4 bar
0
Overflow line "OPEN"
P
+ 0.5 bar
0
Maximum pressure
P
+ 3 bar
0
Filling levels
Insufficient water "ON"
5 %
Insufficient water "OFF"
12 %
Solenoid valve in overflow
90 %
line "CLOSED"
9.2.2
Messages
The display provides alarms in plain text and the ER codes shown in the list. Use
the arrow buttons to scroll through multiple alarms displayed at the same time.
The fault memory stores the last 20 alarms for review,  9.2 "Configuring
settings in the controller",  29.
Alarm causes can be eliminated by the operator or a specialist workshop. If this is
not possible, contact the Reflex Customer Service.

Note!
Clearing of the cause must be confirmed by pressing the "Ack" button on
the operator panel. All other alarms are automatically reset as soon as
the cause has been eliminated.

Note!
Floating contacts, setting in the Customer menu,  9.2 "Configuring
settings in the controller",  29.
Check set value in the Customer or Service menu.
Check water level.
Check compressor.
Set the controller to Automatic mode.
Comment
In the case of soft water residual
capacity = 0
= Target – Actual
Replace cartridge.
Comment
Differential pressured added to
the "P
" minimum operating
0
pressure.
Differential pressured added to
the "P
" minimum operating
0
pressure.
The message is displayed after
the compressor runs for 240
minutes.
Differential pressured added to
the "P
" minimum operating
0
pressure.
Differential pressured added to
the "P
" minimum operating
0
pressure.
Differential pressured added to
the "P
" minimum operating
0
pressure.
Remedy
Alarm
reset
"Quit"