ER
Alarm
Code
02.1
Insufficient water
-
03
High water
YES
04.1
Compressor
YES
05
Compressor run time
-
06
Make-up time
-
07
Make-up cycles
-
08
Pressure measurement
YES
09
Level sensor
YES
10
Maximum pressure
-
11
Make-up volume
-
15
Make-up valve
-
16
Power failure
-
19
Stop ˃ 4 hours
-
20
Max. make-up volume
-
21
Maintenance
-
recommended
24
Softening
-
30
I/O module fault
-
31
EEPROM defective
YES
32
Undervoltage
YES
33
Adjustment parameter
-
faulty
34
Communication
-
Main board faulty
35
Digital input voltage
-
faulty
36
Analogue input voltage
-
faulty
Floating
contact
•
Set value not reached.
•
Make-up disabled.
•
Air in the system.
•
Dirt trap clogged.
•
Set value exceeded.
•
Make-up disabled.
•
Water intake through a leak in a thermal transfer
medium of the user.
•
"RG" and "RG" vessels too small.
•
Compressor disabled.
•
Fuse defective.
•
Set value exceeded.
•
Severe water loss in the system.
•
Air lines leaking.
•
Solenoid valve in the overflow line does not
close.
•
Set value exceeded.
•
Water loss in the system.
•
Make-up line not connected.
•
Make-up rate insufficient.
•
Make-up hysteresis too low.
Set value exceeded.
Controller receives incorrect signal.
Controller receives incorrect signal.
•
Set value exceeded.
•
Pressure relief pipe not functioning.
•
Dirt trap clogged.
"With water meter" must be activated in the Customer
menu.
•
Set value exceeded.
•
Severe water loss in the system.
Contact water meter measures without make-up
request.
No power.
Device is in Stop mode for more than 4 hours.
Set value exceeded.
Set value exceeded.
•
Set value for soft water capacity exceeded.
•
Time interval for replacement of the softening
cartridge exceeded.
•
I/O module defective.
•
Connection between option card and controller
faulty.
•
Option card defective.
•
EEPROM defective.
•
Internal calculation error.
Supply voltage not achieved.
EEPROM parameter memory defective.
•
Connecting cable defective.
•
Main board defective.
Short-circuit of input voltage.
Short-circuit of input voltage.
Reflexomat Basic — 13.11.2020 - Rev. A
Causes
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Check the make-up valve for leaks.
Connect to power supply.
Set the controller to Automatic mode.
Reset the "Make-up volume" meter in the Customer
menu.
Perform maintenance and reset the maintenance counter
upon completion.
Replace the softening cartridges.
Inform Reflex Customer Service.
Inform Reflex Customer Service.
Check power supply.
Inform Reflex Customer Service.
Inform Reflex Customer Service.
Check the wiring at the digital inputs (water meter, for
example).
Check the wiring at the analogue inputs (pressure/level).
Remedy
Check set value in the Customer or Service menu.
Clean the dirt trap.
Check functioning of the "PV1" solenoid valve.
If necessary, manually add water.
Check set value in the Customer or Service menu.
Check functioning of the "WV1" solenoid valve.
Drain water from the "VG" vessel.
Check site heat transfer medium for leaks.
Check set values in the Customer or Service menu.
Replace the fuse.
Check set value in the Customer or Service menu.
Check the water loss and correct, if necessary.
Seal any leak in the air system.
Check functioning of the "PV1" solenoid valve.
Check set value in the Customer or Service menu.
Check water level.
Connect make-up pipe
Check set value in the Customer or Service menu.
Seal any leak in the system.
Connect the plug.
Check functioning of the pressure sensor.
Check the cable for damage.
Check the pressure sensor.
Check functioning of the load cell.
Check the cable for damage.
Connect the plug.
Check set value in the Customer or Service menu.
Check functioning of the pressure relief pipe.
Clean the dirt trap.
Check set value in the Customer or Service menu.
Check water loss in the system and repair, if
necessary.
Controller
Alarm
reset
-
-
"Quit"
-
"Quit"
"Quit"
"Quit"
"Quit"
"Quit"
"Quit"
"Quit"
-
-
"Quit"
"Quit"
"Quit"
-
"Quit"
-
-
-
-
-
English — 31