NAVIPASS Modbus - Accessory
4. NAVISTEM B2000 / B2100 AND RVS 63 EXCHANGE TABLE
4.1. Exchange table
In the case of using a Navipass Modbus on an RVS 63 managing a
generator cascade equipped with an LMU 64 regulator (eg: Modulo control,
Optimagaz G, Condensagaz G, Azurinox). It is not possible to retrieve
information specific to generators. It is possible to access the registers of
the RVS 63 exchange table, see relevant chapter. This contains the cascade
temperatures and setpoints, the states of the generators (absent, released,
not released, faulty), etc.
Modbus register
HMI parameter
(Navipass)
B2000
Decimal
Hexa
B2100
Navipass Gateway
8
8
--
9
9
--
General boiler room
717
2CD
11
General
100
64
Info button*
101
65
8700
Boiler
110
6E
8311
111
6F
8310
112
70
8314
113
71
8316
114
72
8005
116
74
8326*
235
EB
8330*
236
EC
8331
239
EF
8300
240
FO
8301
241
F1
8308
242
F2
8332
243
F3
8333
259
103
8338
260
104
8339
Heating circuit 1
721
2D1
Panel key
300
12C
501 ... 506
120
78
642
123
7B
643
62 / 202
Nb
register
RVS63
1
Modbus parameter (ex : speed)
1
Time out Modbus
3
Time and date
1
Error code
1
Outdoor temperature
1
Generator starting set-point
1
Generator starting temperature
1
Generator return temperature
1
Generator fumes temperature
1
Generator state
1
Generator modulation
2
No. of hours burner
2
No. of starts burner
1
1st burner stage
1
2nd burner stage
1
Boiler pump speed Q1
Hours of operation of the
2
second stage
2
No. to start 2nd stage
No. of hours of operation of the
2
heating
No. of hours of operation of the
2
DHW
1
CC1 operating mode
42
Heating program, zone 1
3
Start of absence date
3
End of absence date
Access
Data
Read. Writ.
 ***
Possible values
0 ... 1227
0 ... 10 000
See explanations
0 ... 999
-40,0 °C ... 50,0 °C
0,0 °C ... 140,0 °C
0,0 °C ... 140,0 °C
0,0 °C ... 140,0 °C
0,0 °C ... 350,0 °C
0 ... 255
0 ... 100 %
0...65535 hours
0...199999
On / of
On / of
0...100%
0...65535 hours
0...199999
0...199999 hours
0...199999 hours
1: permanent confort
2 : permanently reduced
3 :automatic
7 : frost protection
FFFF, 00:00...23:59
FFFF, ddmm
FFFF, ddmm
00ANO0019-G_EN
Displayed
Data
values
type
See chapter §
u16
See chapter §
u16
u16 by
register
[0..999]
u16
[-400..+500]
s16
[0..1400]
u16
[0..1400]
u16
[0..1400]
u16
[0..3500]
u16
[0..255] **
u8
[0..100]
u8
00 ... 65535
u32
00...199999
u32
0....1
u8
0....1
u8
0...100
u8
0....65535
u32
0....199999
u32
0....199999
u32
0....199999
u32
1...3,7
u8
See end of
u16 by
table
register
See end of
u16 by
table
register
See end of
u16 by
table
register