10. APPLICATION EXAMPLES
10.1. Control of boilers in the starting temperature setpoint
Step 1:
Adjust the following settings on the boiler
Configure the H1 input function
on NAVISTEM Bxxxx, parameter 5950
On NAVIPASS, modbus address 228 (0xE4)
Configure contact action H1
on NAVISTEM Bxxxx, parameter 5951
On NAVIPASS, modbus address 229 (0xE5)
Step 2:
Modify the starting temperature setpoint
configure the starting temperature setpoint
on NAVISTEM B3xxx, parameter 1859
on NAVISTEM B2xxx, parameter 5952
On NAVIPASS, modbus address 200 (0xC8)
10.2. Heating circuit control
Example for the heating circuit 1:
Configure the "comfort" ambient temperature
on NAVISTEM Bxxxx or RVS63
Heating circuit 1
on the NAVIPASS Modbus
Heating circuit 1
15.12.2022
INFORMATION:
INFORMATION:
parameter 710
modbus address 135 (0x87)
The following settings must be performed in addition
to the settings listed in the boiler leaflet.
or
with the NAVIPASS modbus
The following settings must be performed in addition
to the settings listed in the boiler leaflet.
NAVIPASS Modbus - Accessory
values
consumption circuit request 1
9 (0x0009)
normally-closed contact (NC)
0 (0x0000)
-- in °C
-- in °C
temperature in tenth °C
(e.g.: 500 (0x01F4) for 50 °C)
values
-- in °C
-- (0x--) in °C