Tank volume setting
> Tank level calibration
●
After finishing the tank volume setting, calibrate the set
tank level. Perform tank level calibration according to the
instructions on the screen.
1. On the screen in step 4 of "Tank volume setting" (P.21),
use the [ ∧ ] or [ ∨ ] button to select Calibration and press
the [ENTER] button.
2. Use the [ ∧ ] or [ ∨ ] button to select the number of
calibration times and press the [ENTER] button.
• To calibrate twice: Select Do 2 point cal.
• To calibrate three times: Select Do 3 point cal.
• To calibrate five times: Select Do 5 point cal.
• In this example, Do 3 point cal is selected to explain the
calibration method.
3. Make sure that the tank is empty and press the [ENTER]
button.
4. Use the [ ∧ ] or [ ∨ ] button to select YES and press the
[ENTER] button.
• When the value storage process is completed, the Value
Stored pop-up window appears.
5. Pour the fuel in half the set fuel volume and press the
[ENTER] button.
• When the tank volume is set to 500 L, pour 250 L.
6. Use the [ ∧ ] or [ ∨ ] button to select YES and press the
[ENTER] button.
• When the value storage process is completed, the Value
Stored pop-up window appears.
7. Pour the fuel up to the set volume and press the [ENTER]
button.
8. Use the [ ∧ ] or [ ∨ ] button to select YES and press the
[ENTER] button.
• When the tank level calibration is successfully completed,
the CALIBRATED pop-up window appears.
22
To "Configuring the settings" (P.8)