1.1 - GUIDELINES ON ELECTRICAL CONNECTIONS
Prepare cable ducts on the installation site.
The cables for the connection of the various devices in a typical plant are listed in the table below and must be suitable for the type
of installation, for example we recommend a cable type H07RN-F for outdoor installation.
CONNECTION
Power supply voltage - receiver
Connection to the control panel
The following table shows the type and size of the allowable cables for the screw terminals of the above type and the tightening
torques:
mm
6.5
in.
0.26
mm
0.2 ... 2.5
2
AWG
24 ... 14
Use copper conductors (mandatory).
Avoid the presence of wires of exposed branches or coming out of the clamp.
6-1620173M - rev. 0 - 30/10/2023
CABLE
2 x 1,5 mm²
2 x 0,5 mm²
0.2 ... 2.5
0.25 ... 2.5
24 ... 14
24 ... 14
Ø 3.5 mm (0.14 in.)
LENGTH
< 20 m
< 20 m
2 x 0.2 ... 0.75
2 x 0.2 ... 0.75
24 ... 14
2 x 24 ... 18
Translated from the original language - English - 5
2 x 0.25 ... 0.75
2 x 0.25 ... 0.75
2 x 24 ... 18
2 x 24 ... 18
N • m
0.5
Ib-in
4.5
2 x 0.5 ... 1.5
2 x 20 ... 16