5.2 - CONNECT THE RECEIVER TO THE CONTROL PANEL
Valim
• Connect the supply voltage (Valim) to the RCOO board.
• Connect the desired output (OUT 1 and/or OUT 2) to the control unit.
You can connect this output to an 8K2 safety edge input or directly into a safety input with normally closed contact (such as a
photocell input or a STOP input).
• Depending on the input type used in the control unit, select the corresponding type with the use of a jumper.
• Set the DIP-SWITCH 1 to select the polarity of the test command.
TEST POLARITY
ON
OFF
• If the control unit is working without a test control, the TEST POLARITY selector must be set to POSITIVE
POLARITY (OFF position).
• In order to realize a protection system type PL "c" -CAT 2 according to EN ISO 13849-1:2015 you need
to connect the test command (Vtest).
CONNECTION OF THE TEST CONTROL
Use the TEST1 input for the test run on the OUT1 output.
Use the TEST2 input for the test run on the OUT2 output.
12 - English - Translated from the original language
OUT 1
NEGATIVE POLARIZATION:
The test control is a fixed 12 or 24V signal, which the control unit brings to 0 to carry out the
system verification.
POSITIVE POLARIZATION:
The test control shall be voltage-free. The control unit shall carry this control at 12 or 24V to
verify the system.
WARNING
OUTPUT WITH NORMALLY
CLOSED CONTACT
OUTPUT 8K2 OHM
Vtest-OUT2 (+)
Vtest (-)
Vtest-OUT1(+)
6-1620173M - rev. 0 - 30/10/2023
12/24Vdc