TN-S-System, TN-C-S-System, TT-System
↻ A connection cable with 5 wires is provided on the device.
↻ Nominal grid voltage matches the VAC nom name plate details.
1 Unfasten the cable fitting for the AC connection [
2 Remove the outer cladding of the AC cables.
3 Push an M8 cable lug onto the PE line.
4 Remove the cover of the AC filter using the 4 screws[
5 Unscrew the screws on the contact bridge and remove the contact bridge[
_T20].
6 Insert the AC cables through the cable fitting into the connection area.
7 Strip the AC lines [approx. 25 mm].
» Make the grid connection.
TN-C system
↻ Connection cable with 4 wires is provided on the device.
↻ Nominal grid voltage matches the VAC nom name plate details.
1 Unfasten the cable fitting for the AC connection [
2 Remove the outer cladding of the AC cables.
3 Insert the AC cables through the cable fitting into the connection area.
4 Strip the AC lines [approx. 25mm].
» Make the grid connection.
4.3.2 Make the grid connection
5 core connection for TN-S system, TN-C-S system, TT-System
↻ Grid connection is prepared.
1 Loosen nut and lock washer at the marked grounding point.
2 Lay the grounding cable onto the grounding point. Secure using the corresponding nut and lock washer [
10 Nm].
3 Connect wires in accordance with the labels on the screw terminal [
4 Check secure fit of all connected cables.
5 Tighten the cable fittings [
6 Secure cover using the 4 screws [
» The device is connected to the power grid.
» NOTE: If there is a 5-core connection, an inserted contact bridge may trigger any RCD that is present. The in-
structions given above must therefore be carefully followed.
4-core connection, TN-C system
↻ Grid connection is prepared.
1 Connect lines in accordance with the labels on the name plate on the screw ter-
minal [
T_45/
10 Nm].
2 Check secure fit of all connected cables.
3 Tighten the cable fittings [
» The device is connected to the power grid.
NOTE
Observe the general grounding recommendation of the existing grid system.
KACO blueplanet gridsave 50.0TL3-S
W_68].
T_15].
W_68].
W_68 /
20 Nm].
_T15 /
2.3 Nm].
W_68 /
20 Nm].
1
4
Fig. 3: 5-core connection
1
Cover
2
Screws for contact bridge
3
Contact bridge
4
Earthing bolt
AC-Seite
DC-Seite
Fig. 4: Terminals
T_45 /
10 Nm].
Fig. 5: 4-pole connection
2
3
W_13/
Page 7