Technical Data - Kaco 50.0TL3-S Manual De Instrucciones

Ocultar thumbs Ver también para 50.0TL3-S:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 33
10

Technical data

10.1
Electrical data
KACO blueplanet gridsave
DC Input levels
Working range
Rated voltage
Starting voltage
Open circuit voltage
Max. input current
Number of strings
Max. short-circuit current (ISC
max.)
Input source feedback current
Polarity safeguard
Ripple current
KACO blueplanet gridsave
AC Output levels
Nominal power
Rated voltage
Voltage range: continuous op-
eration
Rated current
Max. continuous current
Contribution to peak short-
circuit current ip
Initial short-circuit alternating
current (Ik" first single period
effective value)
Rated frequency
Frequency range
Reactive power
cos phi
Number of feed-in phases
Max. voltage range (up to 100
s)
AC overvoltage protection
10.2
General Data
KACO blueplanet gridsave
General electrical data
Max. efficiency
European efficiency
KACO blueplanet gridsave 50.0TL3-S
50.0 TL3-S (B)
50.0 TL3-S (M)
no
50.0 TL3-S (B)
50.0 TL3-S (M)
50.0 TL3-S (B)
50.0 TL3-S (M)
50.0 TL3-S (L)
662 V [@230/400V];
633 V [@220/380V]-1,050 V
765 V
662 V [@230/400V];
633 V [@220/380V]
1,050 V
90 A
1
150 A
90 A
5.0 %
50.0 TL3-S (L)
50.0 kVA [@ 220V];
50.0 kVA [@230V]
230 / 400 V [3/N/PE]
220 V / 380 V [3/N/PE]
165 V - 288 V [PH-N]
3 x 72.2 A [@400V];
3 x 76.0 A [@380V]
3 x 76.5 A
136 A
77,93 A
50/60 Hz
42-68 Hz
0-100 % Snom
0.3 - 1 ind/cap
3
500 V [Ph-Ph]
no
50.0 TL3-S (L)
Charge 97.9 / discharge 98.4 %
Charge 97.5 / discharge 98.2 %
50.0 TL3-S (X)
yes
50.0 TL3-S (X)
50.0 TL3-S (X)
Strona 93

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

50.0 tl3-s b50.0 tl3-s m50.0 tl3-s l50.0 tl3-s x

Tabla de contenido