10.5 Requirement for supply lines and fuse
DC Side
Max. conductor cross-section
Min. cable cross-section
Length of insulation to be stripped off
Tightening torque
Recommended cable type
Fuse size (electrical data)
Fuse size (mechanical data)
Cable diameter for cable fitting
Fitting for DC connection
Torque for cable fitting
Tab. 1: Requirement for supply lines and fuses AC
AC-Seitig
Max. conductor cross-section
Min. cable cross-section
Length of insulation to be stripped off
Tightening torque
Connection type
Ground conductor connection
Fuse protection for installation provided by customer
Fitting for AC connection
Tightening torque
Cable diameter for cable fitting
Tab. 2: Anforderung an Zuleitungen und Sicherungen AC
Interface
Cable diameter for cable fitting
Ethernet connection type
Ethernet cable cross-section
Tab. 3: Requirement for supply lines and DC fuses - interfaces
2
The loop impedance at any point between the installation field and the battery must be Zs <Un / Ia (Un: nominal
AC voltage, Ia: current for triggering device protection within 200 ms).
Strona 96
95 mm²
in accordance with local installation standards
Depending on the cable lug
10 - 20 (HK) / 16 (SH)
NSGAFöu
- Basic
NH1 gPV 160A M, L, XL device version
65 (NH1) mm M, L, XL device version
15 - 21 mm
M32
4 Nm
95 mm² (AL or CU)
35 mm²
2
25 mm
10 Nm
Screw terminal/PE bolt
M8
min. 100 A / max.125 A
M63
20 Nm
32 - 42 mm
11 - 17 (M25) 5 - 9.5 (M16) min
RJ45
0.25 - 0.5 mm²
KACO blueplanet gridsave 50.0TL3-S