CAUTION
Danger caused by exceeding the inrush current.
The device does not have a inrush current limiter on the DC side. Exceeding the maximum permissible inrush
current of 100A can lead to destruction of the device.
The inrush current must be limited to a max. current of 100A using external means. The DC input ca-
pacity of the device is approx. 2mF.
DC link may still be charged link after disconnecting the device from the battery. The limitation of the
inrush current must also be ensured in this scenario.
Failure to observe these warnings may lead to device damage which is not covered by the manufac-
turer warranty.
Blueplanet 50.0TL3 B1 WM OD IIGB
↻ Connection cable with 2 x 1 strands already on the device.
1 Unscrew the cable fitting [
2 Remove the outer cladding of the DC cables.
3 Pass the DC cables through the cable fittings into the connection compartment.
4 Fit DC lines with an M8 ring cable lug [max. width b 20 mm].
5 Open the contact protection cover on the DC- / DC+ connection.
6 Screw the negative (-) cable end onto the DC connection according to the polar-
ity of the battery [
W_13 /
7 Screw the positive (+) cable end onto the DC connection according to the polar-
ity of the battery [
W_13 /
8 Check secure fit of all connected cables.
9 Close the contact protection cover on the DC- / DC+ connection.
10 Make sure that the polarity is correct, and that the inrush current is ensured at
max. 100A.
11 Fit the protective cover and secure using the 4 screws [
12 Tighten the cable fittings [
4.5
Creating equipotential bonding
↻ The device has been installed on the mount.
1 Strip the insulation from the equipotential bonding cable.
2 Check that the connected cable is fitted securely.
» The housing is included in the equipotential bonding.
4.6
Connecting the interfaces
4.6.1 Overview
DANGER
Risk of fatal injury due to electric shock!
Severe injury or death may result from improper use of the interface connections and failure to observe pro-
tection class III.
The SELV circuits (SELV: safety extra low voltage) can only be connected to other SELV circuits with
protection class III.
All interfaces are located on the communication circuit board on the inside of the housing door.
KACO blueplanet gridsave 50.0TL3-S
W_ 36].
6 -12 Nm].
6 - 12 Nm].
W_36 /
4 Nm].
M8
Fig. 8: DC connection B version
T15 /
2.3 Nm].
Fig. 9: Additional grounding point
1 Earthing bolt
M8
20 mm
DC+ DC-
1