Ferroli BlueHelix HiTech RRT H Instrucciones De Uso, Instalación Y Mantenimiento página 318

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Index
Description
P63
Fan on speed
P64
Fan maximum speed
P65
Not implemented
P66
Valve frequency
P67
Installation C(10)3 / C(11)3
P68
Flue parameter
Heating hysteresis after ignition.
P69
(available from MAIN and DSP FW 1.03)
* Restore Factory Values
To restore all the parameters to the factory values, set parameter b29 to 10 and confirm. Turn the
power off for 10 seconds and then back on.
At this point it is necessary to restore parameter b02 and the modified parameters to the correct
value according to the type of boiler. Parameter b27 will be automatically set to 5.
Display Adjustment Menu [DISPLAY]
Here it is possible to set some display pa-
rameters.
[Contrast] - Contrast adjustment
[Brightness] - Brightness adjustment
[Backlight time] - Display lighting duration
[Reset] - Restore factory values
[Lock time]* - Key lock
After keypad inactivity for a time
equal to the set value (minutes), the
symbol
are inhibited.
To reactivate the keypad, press the
buttons
2 seconds.
* This function is available from ver-
sion DSP FW 1.03.
318
Range
DO NOT MODIFY
(The parameters are automatically updated)
DO NOT MODIFY
(The parameters are automatically updated)
--
0 ÷ 2
0 = Disabled
1 = Enable installation C(10)3 - C(11)3
0 ÷ 10 (modify according to flue table)
6 ÷ 30 °C
appears and the buttons
and
together for about
cod. 3541V484 - Rev 02 - 01/2024
BlueHelix HiTech RRT H
DISPLAY
Contrast
Brightness
Backlight time
Lock time
Reset
fig. 41
Default
G20/G230:
18 kW = 160
28 kW = 160
34 kW = 140
45 kW = 140
G30/G31:
18 kW = 152
28 kW = 152
34 kW = 132
45 kW = 136
G20/G230:
18 kW = 140
28 kW = 172
34 kW = 194
45 kW = 180
G30/G31:
18 kW = 134
28 kW = 156
34 kW = 186
45 kW = 172
1
1
0
0
10
5
Max
10m
OFF
EN