INSTALLATION INSTRUCTIONS ( CONTINUED )
Connect to a Power Source
IMPORTANT: The pump is designed for use with a 115-volt AC power source.
Do not attempt installation on a 12-volt, 24-volt or 230-volt system.
Never apply electrical power to the system when any of the coverplates are removed.
connection instructions could result in death or serious injury from shock, fire or
explosion.
IMPORTANT: Electrical wiring and connections must be made only by a
licensed electrician in accordance with national, state and local electrical codes
regarding Class 1, Division 1 requirements as well as NFPA Code 70 and 30.
Other codes may apply.
1.
Install UL Listed, rigid metal conduit and code-specified gasoline and oil-
resistant wire with ground wire from switch box to the pump electrical box,
using proper seal offs.
2.
Remove the electrical coverplate (see Figure 11). Be careful not to damage
gasket.
3.
Route the wiring and conduit to the pump.
4.
Attach wiring to pump wires using provided wire nuts.
5.
Position all wires inside the pump electrical cavity and replace the
coverplate.
Figure 11
10
EN
Observe precautions against electrical shock when servicing the
pump. Always disconnect power before repairing or servicing.
It is important to exercise more than ordinary care with electrical
installation and maintenance. Failure to follow these electrical
Green Ground
Screw