Definition of DIP switch 0/1:
Definition 0
Definition 1
Table 78 Switch positions
ENC1
Code
0
1
2
4
5
7
8
9
A
B
1) Default depending on the model
Table 79 Set the output
S1
S1 Setting
0 - F
0 - F
0 - F
0 - F
1) Default
Table 80 Set the network address
DIP switch
Definition of DIP Switches
Fan OFF temperature when heating (anti-cold air function)
SW1
• [00]: 24°
• [01]: 15 °C
• [10]: 8 °C
• [11]: Reserved
Behaviour of the fan once the room target temperature has been
reached
SW2
• [0]: Fan off
• [1]: Fan on (anti-cold air function deactivated)
Auto restart
SW3
• [0]: Automatic restart on
• [1]: Automatic restart off
Set master and slave unit
SW5
• [00]: Master unit only, no slave unit
• [01]: Master unit (heating)
• [10]: Master unit (cooling)
• [11]: Slave unit
Climate 5000 L • Climate 5000i U/L – 6721841493 (2023/05)
1)
Capacity setting
20
26
32 - 35
36 - 53
54 - 71
72 - 90
91 - 105
109 - 140
141 - 160
161 - 200
S2
Network address
1)
0 - 15
16 - 31
32 - 47
48 - 63
1)
Configuration to the wired room controller
DIP switch
Definition of DIP Switches
Temperature compensation (heating)
SW6
• [00]: 6 °C
• [01]: 2°C
• [10]: 4°C
• [11]: Reserved
1) Default highlighted in bold
Table 81 Definition of DIP Switches
5
Configuration to the wired room controller
Call up the configuration menu and make the settings:
▶ Switch off the air conditioning system.
▶ Keep theCOPY key pressed until a parameter appears in the display.
If several indoor units are detected, the address (e.g. 00) appears
initially.
▶ With the / or . key, select an indoor unit (00... 16) and confirm
with the key.
▶ Select a parameter with the / or . key and confirm with the key.
▶ Press the / or . key to set the parameter and confirm it with the
key, or press the d key to cancel the setting.
To exit the configuration menu:
▶ Press the d key or wait for 15 seconds.
Make the settings in the configuration menu:
▶ Call up the configuration menu.
▶ Select a parameter with the / or . key and confirm with the key.
The factory settings are highlighted in bold in the following table.
Parameters
Description
Tn (n=1,2, ...)
Check the temperature at the indoor unit.
CF
Check the status of the fan.
SP
Set the statistic pressure for the channel wall unit.
• SP1: low
• SP2: middle 1
• SP3: middle 2
• SP4: high
AF
Function test for three to six minutes.
tF
Offset temperature for the Follow me function.
• −5...0...5 °C
tyPE
Restrict the control to specific operating modes:
• CH: do not restrict available operating modes.
• CC: no heating and automatic mode
• HH: only heating and Fan Mode
• NA: no automatic mode
tHI
Maximum value of adjustable temperature
• 25...30 °C
tLo
Minimum value of adjustable temperature
• 17...24 °C
rEC
Switch the control on/off via the remote control.
• ON: on
• OF: off
1)
57