Bombas circuladoras de bajo consumo energético

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 98
GB
Address
Register name
Auto_adapt_min_h
H13
ead
H14
Set_ulBaudRate
H15
Night_time_start_time
H16
Night_time_end_time
18.6 Digital input wiring method
Digital input: Can be used to externally control pump start/stop.
When the external switch is on,
the pump is running
Digital input
Definition
Ranges
Adaptive
1638 ~
minimum lift
16384
value
Baud rate of
modbus
0~2
communication
Night mode start
time
Night mode end
time
Digital input
When the external switch is closed,
the pump is stopped
163
Register actual
Remark
address
(hexadeci mal)
0x062B
"0": 9600
"1": 19200
0x062C
"2": 115200
Default: 115200
The number of minutes
of the day that night
0x062D
mode starts - 60 if it
starts at 01:00
The number of minutes
in a day that night mode
0x062E
ends - 120 if it ends at
02:00