Device B1.
2.
B1 models do not have batteries in the same box, so a battery
module will always be necessary or the user will have them.
Example for an SLC 1500 ADVANCE RT2 B1 and three backup
extension modules 6A0BU000003:
(3 x 14 Ah) = 42 Ah (value for parameter 05).
3 sec.
Output voltage
selection
Non-critical load
output sockets
Backup time for
non-critical load
output sockets
Backup time for all
output sockets
Battery pack Ah
capacity
EPO contact
configuration
Fig. 18. Menú de ajustes.
58
•
•
•
•
(*)
230
O1
240
208
220
DIS
(*)
O2
ENA
O3
0.. 999
DIS
(*)
O4
0.. 999
O5
7.. 999
(*)
AO
O6
AC
OO
ESC
(*)
The values indicated with
are factory default settings.
The settings can only be carried in 'STby' mode (equipment Off and input
voltage present).
To carry out any modification of the configuration, follow the indicated
sequence with the inverter necessarily Off.
To exit the main menu from any position, press buttons
DIS
Programming of output sockets for non-critical loads disa-
bled.
ENA
Programming of output sockets for non-critical loads ena-
bled.
Backup time setting for non-critical load output sockets when operating
in Battery mode.
Default setting is 999.
Backup time setting for all output sockets when operating in Battery
mode.
Default setting is 'DIS', deactivated. Take into consideration that the
available backup will depend on battery charge level
Note: When it is at '0', the backup time will be 10 seconds.
Battery pack Ah. Do not change for standard models and adjust in B1 or
extended backup models (see section ).
Although the device will still work without adjusting this value on the
display, the time shown in minutes will be incorrect and the battery
charging current will not automatically adjust to them.
EPO button contact type setting.
AO
EPO activated when circuit opened.
AC
EPO activated when circuit closed.
+
together.
SALICRU