Descargar Imprimir esta página

GENERGY 5.2KW DC48V Instrucciones De Uso página 59

Sistema solar todo en uno

Publicidad

Idiomas disponibles

Idiomas disponibles

02
AC input voltage
range
03
Output voltage
04
Output frequency
05
Solar supply
priority
06
Overload bypass:
when enabled,
the unit will
transfer to serial
mode if overload
occurs in battery
mode.
07
Auto restart when
overload occurs
08
Auto restart when
over temperature
occurs
10
Charger source
priority
If selected, acceptable AC input voltage range
will be within 90-280VAC.
If selected, acceptable AC input voltage range
will be within 170-280VAC.
When the user uses the device to connect the
generator, select the generator mode.
If selected, acceptable AC input voltage range
will conform to VDE4105 (184-253VAC).
Set the output voltage range (220VAC-
240VAC)
Solar power provides power for battery
charging as a priority. When the mains is
available, if the battery voltage is lower than
setting point in program 21, the solar energy
will never supply to the load or feed into the
mains, only charge the battery.
If the battery voltage is higher than the setting
point in program 21, the solar energy will
supply to the load or feed into the mains or
recharge the battery.
Solar energy provides power to the loads as
first priority. If the battery voltage is lower than
the setting point in program 20, the solar
energy will never supply to the load or feed
into the mains, only charge the battery. If the
battery voltage is higher than the setting point
in program 20, the solar energy will supply to
the load or feed into the mains or recharge the
battery.
In this inverter/charger is working in Serial, Standby or Fault
mode, charger source can be programmed as below:
Solar energy will charge battery as first
priority. Mains will charge battery only when
solar energy is not available.
Solar energy and mains will charge battery at
the same time.
Solar energy will be the only charger source
no matter mains is available or not.
If this inverter/charger is working in battery mode, only solar
energy can charge battery. Solar energy will charge battery if it
is available and sufficient.
57

Publicidad

loading

Productos relacionados para GENERGY 5.2KW DC48V

Este manual también es adecuado para:

2/3kw dc24v