11
Maximum
charging current:
to configure total
charging current
for solar and
mains chargers
(=mains charging
current + solar
charging current)
13
Maximum utility
charging current
14
Battery type
17
Bulk charging
voltage
18
Floating charging
voltage
19
Low DC cut off
battery voltage
setting
Setting range is from 1A to 80A.
Increment of each click is 1A.
Setting range is from 1A to 60A. Increment of
each click is 1A.
If "User-Defined" LI is selected, battery charge voltage and low
DC cut-off voltage can be set up in program 17, 18 and 19.
If "User-Defined" LI is selected in program 14, this program can
be set up. Setting range is from 24.0V to 29.2V for 24Vdc model.
Increment of each click is 0.1V.
If "User-Defined" LI is selected in program 14, this program can
be set up. Setting range is from 48.0V to 58.4V for 48Vdc model.
Increment of each click is 0.1V.
If "User-Defined" LI is selected in program 14, this program can
be set up. Setting range is from 24.0V to 29.2V for 24Vdc model.
Increment of each click is 0.1V.
If "User-Defined" LI is selected in program 14, this program can
be set up. Setting range is from 48.0V to 58.4V for 48Vdc model.
Increment of each click is 0.1V.
If "User-Defined" LI is selected in program 14, this program can
be set up. Setting range is from 20.0V to 24.0V for 24Vdc model.
Increment of each click is 0.1V. Low DC cut off voltage will be
fixed to setting value no matter what percentage of load is
connected.
If "User-Defined" LI is selected in program 14, this program can
be set up. Setting range is from 48.0V to 58.4V for 48Vdc model.
Increment of each click is 0.1V. Low DC cut off voltage will be
fixed to setting value no matter what percentage of load is
connected.
58