2 Safety
2
Safety
2.1
Intended Use
The Sunny Boy is a transformerless PV inverter which converts the direct current of the PV array to
grid-compliant alternating current and feeds it into the utility grid.
The product is suitable for indoor and outdoor use.
The product must only be operated with PV arrays (PV modules and cabling) that are approved by
the electrical standards applicable on-site and the National Electrical Code
the Canadian Electrical Code
No galvanic isolation
The product is not equipped with a transformer and therefore has no galvanic isolation.
• Do not operate grounded PV modules together with the product. If grounded PV modules
are connected to the product, an event will occur which will appear on the product
display. The event will also be displayed, along with the associated message, in the event
list on the user interface of the product.
• Only ground the mounting frames of the PV modules.
• The neutral conductor of the AC output is not bonded to ground within the product.
• The neutral conductor of the AC output for secure power supply operation is bonded to
ground within the product.
PV modules with a high capacity to ground may only be used if their coupling capacity does not
exceed 2.5 μF.
To protect the PV system against excessive reverse currents under fault conditions, a DC-side
overcurrent protective device must be connected in accordance with the National Electrical Code
to prevent any short-circuit currents that exceed the ampacity of the DC electric circuit or the
maximum series fuse rating of the PV modules. Typically, string fuses are used if more than two
strings are connected in parallel.
All components must remain within their permitted operating ranges and their installation
requirements at all times.
The product is approved for the US and Canadian market.
Use SMA products only in accordance with the information provided in the enclosed
documentation and with the locally applicable laws, regulations, standards and directives. Any
other application may cause personal injury or property damage.
Alterations to the SMA products, e.g., changes or modifications, are only permitted with the express
written permission of SMA Solar Technology AG. Unauthorized alterations will void guarantee and
warranty claims and in most cases terminate the operating license. SMA Solar Technology AG
shall not be held liable for any damage caused by such changes.
Any use of the product other than that described in the Intended Use section does not qualify as the
intended use.
The enclosed documentation is an integral part of this product. Keep the documentation in a
convenient, dry place for future reference and observe all instructions contained therein.
8
SBxx-1SP-US-41-IA-xx-10
®
CSA C22.1.
SMA Solar Technology AG
®
ANSI/NFPA 70 or
Installation Manual
®