Figure 4.12 Full EMC precautions
The above guidelines are applicable to all drive sizes.
NOTE
For further information on the cable screening brackets and screening clamps kit, refer
to the Commander SE Advanced User Guide and the EMC Data sheets which are
available from Control Techniques' Drive Centres and Distributors.
4.5.3

Special requirements

Special considerations are required for the following requirements:
Meeting the residential emission standard, EN50081-1 (Size 1 only)
One of the footprint filters (part number 4200-6102 or 4200-6103) must be used.
Interruptions to the motor cable
The motor cable should ideally be a single run of shielded cable having no interruptions.
In some situations it may be necessary to interrupt the cable, for example to connect the
motor cable to a terminal block within the drive enclosure, or to fit an isolator switch to
allow safe working on the motor. In these cases both motor cable shield connections
must be clamped directly to the back-plate or other flat metallic structure, as illustrated
in Figure 4.13 and Figure 4.14. Keep the length of unscreened power conductors to a
minimum, keep them as close as possible to the metal plate, and ensure that all
sensitive equipment and circuits are at least 0.3m (12in) away from them.
34
Commander SE User Guide
www.controltechniques.com
Issue Number 9