6. Accessories
6.1
Level indicator, order no. 11503
7. Maintenance and inspection
7.1
Safety measures
i
Important:
The operator must provide any protective clothing that may be required.
Who can carry out maintenance and inspection work?
» Normal maintenance work can be carried out by trained operating personnel.
i
Important:
Inspections of the filling station may only be carried out by an authorised, registered inspection
agency with respect to the ADR approval.
7.2
Maintenance and inspection table
Interval
Assembly
As re-
Outside of fill-
quired
ing station
Container
Monthly
Line/hose
system
Moving parts of
the tank
Annually
Leakage probe
Every two
and a half
Filling station
years
Every five
Filling station
years
7.3
Explanations regarding recurring tests and inspections
In accordance with ADR 6.5.4.4.1 b), the DT-Mobil Easy system must undergo inspection to the satisfac-
tion of the responsible authority at intervals not exceeding two and a half years with regard to the external
condition and proper function of the operating equipment.
Action
Remove any adhering dirt and diesel fuel.
Repair damage to the zinc coating by cold galvanising or repair damage to
the paint with 2-component PU paint RAL 7036 "platinum grey".
Visual check for damage
Check hoses for cracks and porosity, check valves for leaks (replace
defective parts).
Lubricate hinges and lock with a few drops of universal oil.
Visual and functional check as described in the LS-03 leakage probe
operating instructions.
Inspection according to ADR 6.5.4.4.1 b) and 6.5.4.4.2
- Documentation in the test report (see section 10)
- If the test is successful – entry with waterproof pen on type plate – imprint
on type plate (month/year)
Inspection according to ADR 6.5.4.4.1 a) and 6.5.4.4.2
- Documentation in the test report (see section 10)
- If the test is successful – imprint on type plate (month/year)