Technical Data - SMA GRID-CONNECT-BOX 12 Instrucciones De Funcionamiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

12 Technical Data

12 Technical Data
Connection to utility grid
Number of terminals
Rated grid input power
Rated operating voltage between L and N
Rated operating voltage between L1 and L2
Rated current / AC input current
Terminals for connection N, PE, L1, L2, L3
Minimum connectable conductor cross-section
Maximum connectable conductor cross-section
Fuse
Maximum permitted fuse rating for F330
Unaffected short-circuit current / relative rated short-circuit current at the terminals
Maximum permitted rated current of the back-up fuse
Short-circuit current breaking capacity of the back-up fuse
Forward current of the back-up fuse
Multicluster-Box connection
Number of terminals
Rated grid input power
Rated operating voltage between L and N
Rated operating voltage between L1 and L2
Rated current / AC input current
Terminals for connection N, PE, L1, L2, L3
Minimum connectable conductor cross-section
Maximum connectable conductor cross-section
Unaffected short-circuit current / relative rated short-circuit current at the terminals
Maximum permitted rated current of the back-up fuse
Short-circuit current breaking capacity of the back-up fuse
Forward current of the back-up fuse
Connection of grounding
Terminal for grounding conductor connection
32
GRID-BOX-12-3-20-BE-xx-12
SMA Solar Technology AG
1 x three-phase
138 kW
230 V
400 V
3 x 200 A
Spring-cage terminals
50 mm²
150 mm²
LV/HRC 1
200 A gG
≤17 kA
200 A gG
≥25 kA
≤17 kA
1 x three-phase
138 kW
230 V
400 V
3 x 200 A
Spring-cage terminals
50 mm²
150 mm²
≤17 kA
200 A gG
≥25 kA
≤17 kA
Spring-cage terminals
Operating manual