No.
Name
(Hex.)
A1-02
Control Method
Selection
A1-03
Initialize Parameters
b1-01
Frequency Reference
Selection 1
b1-02
Run Command
Selection 1
b1-03
Stopping Method
Selection
b1-04
Reverse Operation
Selection
C1-01
Acceleration Time 1
RUN
C1-02
Deceleration Time 1
RUN
C2-01
S-Curve Time @
Start of Accel
C2-02
S-Curve Time @
End of Accel
C2-03
S-Curve Time @
Start of Decel
C2-04
S-Curve Time @
End of Decel
C6-01
Normal / Heavy
Duty Selection
YASKAWA TOMPC7106173UA GA500 Installation and Operation Instruction
Sets the control method for the drive application and the motor.
0: V/f Control, 2: Open Loop Vector, 5: PM Open Loop Vector,
6: PM Advanced Open Loop Vector, 8: EZ Vector Control
Sets parameters to default values.
0: No Initialization, 1110: User Initialization, 2220: 2-Wire Initialization,
3330: 3-Wire Initialization
Sets the input method for the frequency reference.
0: Keypad, 1: Analog Input, 2: Memobus/Modbus Communications,
3: Option PCB, 4: Pulse Train Input
Sets the input method for the Run command.
0: Keypad, 1: Digital Input, 2: Memobus/Modbus Communications,
3: Option PCB
Sets the method to stop the motor after removing a Run command or
entering a Stop command.
0: Ramp to Stop, 1: Coast to Stop, 2: DC Injection Braking to Stop,
3: Coast to Stop with Timer, 9: Stop with Constant Distance
Sets the reverse operation function. Disable reverse operation in fan or
pump applications where reverse rotation is dangerous.
0: Reverse Enabled, 1: Reverse Disabled
Sets the length of time to accelerate from zero to maximum output
frequency.
Sets the length of time to decelerate from maximum output frequency to
zero.
Sets the S-curve acceleration time at start.
Sets the S-curve acceleration time at completion.
Sets the S-curve deceleration time at start.
Sets the S-curve deceleration time at completion.
Sets the drive duty rating.
0: Heavy Duty Rating, 1: Normal Duty Rating
Description
1 English