Descargar Imprimir esta página

YASKAWA CIPR-GA50C Serie Manual De Instrucciones página 383

Ocultar thumbs Ver también para CIPR-GA50C Serie:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 164
*2
If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use the
closed-loop crimp terminals to connect a protective ground wire that has a minimum cross-sectional area of
10 mm
2
(copper wire).
Main Circuit Wire Gauges and Tightening Torques (for UL Standards)
Single-Phase 200 V Class
Model
Terminal
L/L1, N/L2
U/T1, V/T2, W/T3
B001
-, +1
B1, B2
L/L1, N/L2
U/T1, V/T2, W/T3
B002
-, +1
B1, B2
YASKAWA TOMPC7106173UA GA500 Installation and Operation Instruction
Recomm.
Applicable
Gauge
Gauge
AWG, kcmil
AWG, kcmil
14
14
14
14
14
14
14
14
*2
14
14
14
14
14
14
14
14
14
14
*2
14
14
Wire
Stripping
*1
Length
mm
6.5
6.5
6.5
6.5
*2
-
6.5
6.5
6.5
6.5
*2
-
10 Attachment
Terminal
Tightening
Screw
Torque
Size and
N∙m (lbf∙in)
Shape
0.5 - 0.6
M3
(4.4 - 5.3)
0.5 - 0.6
M3
(4.4 - 5.3)
0.5 - 0.6
M3
(4.4 - 5.3)
0.5 - 0.6
M3
(4.4 - 5.3)
0.8 - 1.0
M3.5
(7.1 - 8.9)
0.5 - 0.6
M3
(4.4 - 5.3)
0.5 - 0.6
M3
(4.4 - 5.3)
0.5 - 0.6
M3
(4.4 - 5.3)
0.5 - 0.6
M3
(4.4 - 5.3)
0.8 - 1.0
M3.5
(7.1 - 8.9)
383

Publicidad

loading

Este manual también es adecuado para:

Ga500