No.
Name
(Hex.)
H3-01
Terminal A1 Signal
Level Select
H3-02
Terminal A1
Function Selection
H3-03
Terminal A1 Gain
Setting
RUN
H3-04
Terminal A1 Bias
Setting
RUN
H3-09
Terminal A2 Signal
Level Select
H3-10
Terminal A2
Function Selection
H3-11
Terminal A2 Gain
Setting
RUN
H3-12
Terminal A2 Bias
Setting
RUN
H3-13
Analog Input
FilterTime Constant
H3-14
Analog Input
Terminal Enable Sel
H4-01
Terminal AM Analog
Output Select
H4-02
Terminal AM Analog
Output Gain
RUN
H4-03
Terminal AM Analog
Output Bias
RUN
H4-07
Terminal AM Signal
Level Select
L1-01
Motor Overload
(oL1) Protection
YASKAWA TOMPC7106173UA GA500 Installation and Operation Instruction
Sets the input signal level for MFAI terminal A1.
0: 0 to 10V (Lower Limit at 0), 1: 0 V to 10 V (Without Lower Limit)
Sets a function for MFAI terminal A1.
Sets the gain of the analog signal input to MFAI terminal A1.
Sets the bias of the analog signal input to MFAI terminal A1.
Sets the input signal level for MFAI terminal A2.
0: 0-10V (LowLim=0), 1: 0 V to 10 V (Without Lower Limit),
2: 4 to 20 mA, 3: 0 to 20 mA
Sets a function for MFAI terminal A2.
Sets the gain of the analog signal input to MFAI terminal A2.
Sets the bias of the analog signal input to MFAI terminal A2.
Sets the time constant to apply a primary delay filter to the MFAI terminal.
Sets the enabled terminal or terminals when H1-xx = C [MFDI Function
Select = Analog Terminal Enable Selection] is ON.
1: Terminal A1 only, 2: Terminal A2 only, 7: All Terminals Enabled
Sets the monitoring number to be output from the MFAO terminal AM.
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
Sets the bias of the monitor signal that is sent from MFAO terminal AM.
Sets the MFAO terminal AM output signal level.
0: 0 to 10 V, 2: 4 to 20 mA
Sets the motor overload protection with electronic thermal protectors.
0: No, 1: Variable Torque, 2: Constant Torque 10:1 Speed Range,
3: Constant Torque 100:1 SpeedRange, 4: PM Variable Torque,
5: PM Constant Torque, 6: Variable Torque (50Hz)
Description
1 English
31