10 Attachment
*1
Remove insulation from the ends of wires to expose the length of wire shown.
*2
If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use the
closed-loop crimp terminals to connect a protective ground wire that has a minimum cross-sectional area of
10 mm
2
(copper wire).
■
Three-Phase 400 V Class
Model
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4001
-, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4002
-, +1, +2
B1, B2
378
Recomm.
Applicable
Gauge
Gauge
mm
2
mm
2.5
2.5 - 4
2.5
2.5 - 4
2.5
2.5 - 4
2.5
2.5 - 4
*2
2.5
2.5 - 6
2.5
2.5 - 4
2.5
2.5 - 4
2.5
2.5 - 4
2.5
2.5 - 4
*2
2.5
2.5 - 6
YASKAWA TOMPC7106173UA GA500 Installation and Operation Instruction
Wire
Stripping
*1
Length
2
mm
8
8
8
8
*2
-
8
8
8
8
*2
-
Terminal
Tightening
Screw
Torque
Size and
N∙m (lbf∙in)
Shape
0.5 - 0.6
M3
(4.4 - 5.3)
0.5 - 0.6
M3
(4.4 - 5.3)
0.5 - 0.6
M3
(4.4 - 5.3)
0.5 - 0.6
M3
(4.4 - 5.3)
1.2 - 1.5
M4
(10.6 - 13.3)
0.5 - 0.6
M3
(4.4 - 5.3)
0.5 - 0.6
M3
(4.4 - 5.3)
0.5 - 0.6
M3
(4.4 - 5.3)
0.5 - 0.6
M3
(4.4 - 5.3)
1.2 - 1.5
M4
(10.6 - 13.3)