NOTICE
resistance grounding, or asymmetric-grounding network, put the EMC Filter screw or screws in the OFF
position to disable the built-in EMC filter. If you do not disable the built-in EMC filter, it will cause damage
to the drive.
If you lose an EMC filter switch screw, use
screw and install the new screw with the correct tightening torque.
NOTICE
approved, it can cause damage to the drive.
Model
B001 - B004
2001 - 2006
B006 - B012
2008 - 2021
4001 - 4012
2030 - 2082
4018 - 4060
Safe Disable Input
The TÜV mark identifies that the product complies with the safety standards.
46
Figure 1.8 Symmetric Grounding
Damage to Equipment. When you use the drive with a non-grounding, high-
Only use the screws specified in this manual. If you use screws that are not
Table 1.10 Screw Sizes and Tightening Torques
Figure 1.9 TÜV Mark
YASKAWA TOMPC7106173UA GA500 Installation and Operation Instruction
Table 1.10
to find the correct replacement
Screw Size
M3 × 16
M3 × 20
M4 × 20
Tightening Torque
N∙m (lbf∙ in)
0.5 - 0.7
(4.4 - 6.2)
0.5 - 0.7
(4.4 - 6.2)
1.0 - 1.3
(8.9 - 11.5)