14 Technical Data
AC voltage range
Nominal AC current at 277 V
Maximum output current
Total harmonic distortion of the output current
with total harmonic distortion of the AC voltage
< 2%, and AC power > 50% of the rated power
Maximum residual output current
Duration of the maximum residual output current
Line synchronization characteristics / In-rush cur-
rent
Rated power frequency
Operating range at AC power frequency 60 Hz
Maximum utility backfeed current to utility
Limits of accuracy of voltage measurement
Limits of accuracy of frequency measurement
Limits of accuracy of time measurement at nomi-
nal trip time
Limits of accuracy of current measurement
Limits of accuracy of power (active/reactive)
measurement
Limits of accuracy of power factor measurement
Limits of accuracy of time measurement
Output power at +60°C (+140°F)
Maximum power operating ambient tempera-
ture
Power factor at rated power
Displacement power factor, adjustable
Feed-in phases
Phase connection
Overvoltage category in accordance with
UL1741
74
STPTL-US-10-IA-xx-20
SMA Solar Technology America LLC
STP 24000TL-US-10
244 V to 305 V
29 A
29 A
≤3%
142.5 A
pk
0.0310 s
Method 2
60 Hz
59.3 Hz to 60.5 Hz
–
2% ACVolt
±0.05 Hz
±0.5%
1% ACCur
5% rated Power
0.01
0.001 s
17000 W
+45°C (+113°F)
1
0
to 0
overexcited
underexcited
3
3
IV
STP 30000TL-US-10
244 V to 305 V
36.2 A
36.2 A
≤3%
79.8 A
pk
0.0310 s
Method 2
60 Hz
59.3 Hz to 60.5 Hz
–
2% ACVolt
±0.05 Hz
±0.5%
1% ACCur
5% rated Power
0.01
0.001 s
21270 W
+45°C (+113°F)
1
0
to 0
overexcited
underexcited
3
3
IV