CONFIGURATION
The following table shows all the possible configurations available to adapt the UPS to the user's
requirements.
KEY:
=
=
FUNCTION
To select the nominal
Output frequency
output frequency
To select the nominal
Output voltage
To select one of the 4
Operating mode
different operating
automatic restart after
Start-up delay
the mains returns
Automatic shutdown
Shutdown due to
operation from the
minimum load
battery if the load is
Maximum time of
Back up time
operation from the
limit
Estimated remaining
End of discharge
back up time for the
alert
end of discharge alert
Time interval for the
Battery test
automatic battery test
Indicates that the configuration can be changed from the display panel as well
as by means of the configuration software.
Indicates that the configuration can only be changed via the configuration
software.
DESCRIPTION
PREDEFINED
Auto
230V
output voltage
ON LINE
modes
Delay before
5 sec.
of the UPS in
Disabled
less than 5%
Disabled
battery
3 min.
40 hours
POSSIBLE CONFIGURATIONS
50 Hz
60 Hz
Auto: automatic sensing from the input
frequency
220V
230V
240V
220 ÷ 240 in 1V steps
(only via software)
ON LINE
ECO
SMART ACTIVE
STAND-BY OFF
Disabled
1 ÷ 255 in 1 sec. steps
Enabled
Disabled
Disabled (full battery discharge)
1 ÷ 65000 in 1 sec. steps
1 ÷ 255 in 1 min. steps
Disabled
1 ÷ 1000 in 1 hour steps