LAYOUT DIAGRAM WITH VAPORISATION
eventual emergency gas phase connection
E
N
G
L
Warnings
- The vaporizer is considered a dangerous point and should the-
I
refore be situated at a safe distance from any building.
- The electrical system must be AD-EP (anti-deflagration-explosion
S
proof).
- The L.P.G. pipelines must be made of SS steel with welded or
H
flanged joints NP 40 (nominal pressure 40 bar). Threaded joints
are prohibited.
OPERATING ANOMALY
TYPE OF IRREGULARITY
The burner does not
start.
The burner starts but the
flame does not ignite.
The burner stops conse-
quently.
The burner starts and
the flame ignites then the
burnes stops.
tank
PROBABLE CAUSE
1) Lack of currente.
2) Gas does not reach the bur-
ner.
1)The gas valves do not open.
2) There is no spark at the electro-
de.
3) The air pressure switch does
not give it's consent to the control
box.
1) The control electrode does
not detect or detects the flame
improperly.
0006080895_200903
vaporizer
1st stage reducer unit
Specific materials
1) Liquid recovery valve.
2) Liquid delivery cock with flow limiter.
3) Steel fitting with welded tang and copper washer.
4) 18 bar safety valve with welded steel fitting.
1) Check the fuses of the feed line. Check
the fuses of the control box. Check the line
of the thermostats and the gas pressure
switch.
2) Check the opening of the detecting devi-
ces located along the feeding pipes.
1) Check the valves operation.
2) Check the operation of the ignition tran-
sformer. Check the position of the electrodes
ends.
3) Check the setting and operation of the air
pressure switch.
1) Check the position of the control elec-
trode. Check the valve of the ionisation
current.
20 / 20
RIMEDY