1.9 INDOOR INSTALLATION.
• Type C configuration, sealed chamber and
fan assisted.
Horizontal intake - exhaust kit Ø60/100. Kit
assembly (Fig. 1-15): install the bend with flange
(2) onto the central hole of the boiler inserting
the gasket (1) and tighten using the screws in the
kit. Couple the terminal pipe (3) with the male
end (smooth) into the female end of the bend
(with lip seals) up to the stop; making sure that
the internal wall sealing plate and external wall
sealing plate have been fitted, this will ensure
sealing and joining of the elements making up
the kit.
Note: when the boiler is installed in areas where
very rigid temperatures can be reached, a special
anti-freeze kit is available that can be installed as
an alternative to the standard kit.
• Coupling extension pipes and concentric
elbows Ø 60/100. To snap-fit extensions with
other elements of the flue extraction elements,
operate as follows engage the concentric pipe
or elbow with the male side (smooth) on the
female section (with lip seal) up to the stop
on the previously installed element. This will
ensure sealing and joining of the elements cor-
rectly.
The Ø 60/100 horizontal intake/exhaust kit can
be installed with the rear, right side, left side and
front outlet.
• Application with rear outlet (Fig. 1-16). The
970 mm pipe length enables routing through
a maximum thickness of 775 mm. Normally
the terminal must be shortened. Calculate the
distance by adding the following values: Part
thickness
internal projection
projection. The minimum indispensable pro-
jection values are given in the figure.
2
3
1
The kit includes:
N°1 - Gasket (1)
N°1 - Concentric bend 90° (2)
N°1 - Intake-exhaust concentric pipe
N°1 - Internal white wall sealing plate (4)
N°1 - External grey wall sealing plate (5)
Fig. 1-15
• Application with side outlet (Fig. 1-17); Using
the horizontal intake-exhaust kit, without the
special extensions, enables routing through
a wall thickness of 725 mm with the left side
outlet and 645 with the right side outlet.
• Extensions for horizontal kit. The horizontal
intake-exhaust kit Ø 60/100 can be extended
up to a max. horizontal distance of 3,000 mm
including the terminal with grid and excluding
the concentric bend leaving the boiler. This
configuration corresponds to a resistance fac-
tor of 100. In these cases the special extensions
must be requested.
Connection with N°1 extension (Fig. 1-18).
Max. distance between vertical boiler axis and
external wall is 1855 mm.
Connection with N°2 extensions (Fig. 1-19).
Max. distance between vertical boiler axis and
external wall is 2805 mm.
Horizontal intake-exhaust kit Ø 80/125. Kit
assembly (Fig. 1-20): install the bend with flange
(2) onto the central hole of the boiler inserting
the gasket (1) and tighten using the screws in the
kit. Fit the male end (smooth) of the adapter (3)
up to the stop on the female end of the bend (2)
(with lip seal). Fit the Ø 80/125 (4) concentric
terminal pipe with the male end (smooth) to the
female end of the adapter (3) (with lip gasket) up
to the stop; making sure that the internal wall
sealing plate and external wall sealing plate have
been fitted, this will ensure sealing and joining
of the elements making up the kit.
external
C12
4 5
Ø 60/100 (3)
C12
Fig. 1-17
• Coupling extension pipes and concentric
elbows Ø 80/125. To snap-fit extensions with
other elements of the flue extraction elements,
operate as follows engage the concentric pipe
or elbow with the male side (smooth) on the
female section (with lip seal) up to the stop
on the previously installed element. This will
ensure sealing and joining of the elements cor-
rectly.
Important: if the exhaust terminal and/or exten-
sion concentric pipe needs shortening, consider
that the internal pipe must always protrude by 5
mm with respect to the external pipe.
Normally the Ø 80/125 horizontal intake-exhaust
kit is used if particularly long extensions are re-
quired; the Ø 80/125 kit can be installed with.
• Extensions for horizontal kit. The Ø 80/125
horizontal intake-exhaust kit can be extended
up to a max. horizontal distance of 7,300 mm
including the terminal with grid and excluding
the concentric bend leaving the boiler and the
adapter Ø 60/100 in Ø 80/125 (Fig. 1-21). This
configuration corresponds to a resistance factor
of 100. In these cases the special extensions
must be requested.
N.B.: when installing the ducts, a section clamp
with pin must be installed every 3 metres.
• External grill. N.B.: for safety purposes, do not
even temporarily obstruct the boiler intake/
exhaust terminal.