6.11 "ONE MIXED ZONE AND ONE DIRECT ZONE – NO EXTERNAL SENSOR"
Autoconfi guration:
Connection
Description
Pump phase (RY1)
7
Pump neutral (RY1)
8
Mixing Valve Opening phase (RY2)
9
Mixing Valve neutral (RY2)
10
Mixing Valve Closing phase (RY3)
11
Pump phase (RY4)
12
Pump neutral (RY5)
14
On/Off Thermostat or Remote Control (RT1)
19
On/Off Thermostat or Remote Control (RT1)
20
On/Off Thermostat or Remote Control (RT2)
21
On/Off Thermostat or Remote Control (RT2)
22
NTC sensor (T1)
25
NTC sensor (T1)
26
NTC sensor (T3)
29
NTC sensor (T3)
30
Card SK connected
X15
The algorithm remains the same as the confi guration: 6.1 "ONE Direct Zone – No External Sensor".
The algorithm of the Mixed Zone remains the same as the confi guration: 6.7 "ONE Mixed Zone – No External Sensor".
What changes is:
a. The calculation of Zone card Heating Setpoint
In case of simultaneous request, the Zone card Heating Setpoint is equal to the higher of the two: Zone1 Heating Setpoint and Zone2 Heating Setpoint.
If the zone that ends the request has the higher Heating Setpoint, the Zone card Heating Setpoint must be immediately decreased until it is equal to the Heating
Setpoint of the zone still in request status.
If the zone that starts the request has a higher Heating Setpoint than the zone already in request status, the Zone card Heating Setpoint must be immediately increased
until it is equal to the higher Heating Setpoint of the zone in request status.
b. Each zone has its own adjustment sensors and parameters.
c. Post-circulation time
This must be carried out only on the last zone that ends the request.
Also, if the last zone in request status is doing post-circulation and another zone starts its own request, post-circulation must be stopped whereas the mixing valve
must be closed for the entire duration of the Mixing valve closing Time timer (TSP31): so that there is always and only a single zone in post-circulation.
6.12 "ONE MIXED ZONE AND ONE DIRECT ZONE – WITH EXTERNAL SENSOR"
Autoconfi guration:
Connection
Description
Pump phase (RY1)
7
Pump neutral (RY1)
8
Mixing Valve Opening phase (RY2)
9
Mixing Valve neutral (RY2)
10
Mixing Valve Closing phase (RY3)
11
Pump phase (RY4)
12
Pump neutral (RY5)
14
On/Off Thermostat or Remote Control (RT1)
19
On/Off Thermostat or Remote Control (RT1)
20
On/Off Thermostat or Remote Control (RT2)
21
On/Off Thermostat or Remote Control (RT2)
22
NTC sensor (T1)
25
NTC sensor (T1)
26
NTC sensor (T3)
29
NTC sensor (T3)
30
NTC sensor (T4)
30
NTC sensor (T4)
31
Card SK connected
X15
The algorithm remains the same as the confi guration: 6.11 "ONE Mixed Zone and ONE Direct Zone – No External Sensor".
What changes is only the calculation of Zone1 Heating Setpoint and Zone2 Heating Setpoint if the sliding temperature was activated in one or both zones.
6.13 "ONE MIXED ZONE AND TWO DIRECT ZONES – NO EXTERNAL SENSOR"
Autoconfi guration:
Connection
Description
Pump phase (RY1)
7
Pump neutral (RY1)
8
Mixing Valve Opening phase (RY2)
9
Mixing Valve neutral (RY2)
10
Mixing Valve Closing phase (RY3)
11
Pump phase (RY4)
12
Pump phase (RY5)
13
Mixed zone 1
Mixed zone 1
Mixed zone 1
Mixed zone 1
Mixed zone 1
Direct Zone 1
Direct Zone 1
Mixed zone 1
Mixed zone 1
Direct zone 1
Direct zone 1
Mixed zone 1 delivery
Mixed zone 1 delivery
Heating delivery
Heating delivery
Mixed zone 1
Mixed zone 1
Mixed zone 1
Mixed zone 1
Mixed zone 1
Direct zone 1
Direct zone 1
Mixed zone 1
Mixed zone 1
Direct zone 1
Direct zone 1
Mixed zone 1 delivery
Mixed zone 1 delivery
Heating delivery
Heating delivery
External probe
External probe
Mixed zone 1
Mixed zone 1
Mixed zone 1
Mixed zone 1
Mixed zone 1
Direct zone 1
Direct zone 2
CONTROLLO ZONE FZ4B