Grundfos SP Serie Instrucciones De Instalación Y Operación página 39

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

10.4.5 575 V, 3-phase, 60 Hz
Maximum submersible power cable length (maximum cable length in feet, starter to motor)
Motor
[Hp]
rating
14
12
5900
9410
5
(1798)
(2868)
4270
6810
.75
(1301)
(2076)
3630
5800
1
(1106)
(1768)
2620
4180
1.5
(799)
(1274)
2030
3250
2
(619)
(991)
1580
2530
3
(482)
(771)
920
1480
5
(280)
(451)
660
1060
7.5
(201)
(323)
490
780
10
(149)
(238)
330*
530
15
(101*)
(162)
410*
20
-
575 V
(125*)
3-ph
60 Hz
25
-
-
30
-
-
40
-
-
50
-
-
60
-
-
75
-
-
100
-
-
125
-
-
150
-
-
175
-
-
200
-
-
Note:
* Indicates single conductor only (not jacketed).
No asterisk indicates both jacketed cable and
single-conductor cables.
The table is based on copper wire. If
aluminum wire is used, multiply lengths by
0.5.
The maximum permissible length of
aluminum is considerably shorter than
copper wire of same size.
AWG copper wire size
10
8
6
4
-
-
-
-
-
-
-
-
9120
-
-
-
(2780)
6580
-
-
-
(2006)
5110
8060
-
-
(1558)
(2457)
3980
6270
-
-
(1213)
(1911)
2330
3680
5750
-
(710)
(1122)
(1753)
1680
2650
4150
-
(512)
(808)
(1265)
1240
1950
3060
4770
(378)
(594)
(933)
(1454)
850
1340
2090
3260
(259)
(408)
(637)
(994)
650
1030
1610
2520
(198)
(314)
(491)
(768)
520
830
1300
2030
(158)
(253)
(396)
(619)
430*
680
1070
1670
(131*)
(207)
(326)
(509)
500*
790
1240
-
(152*)
(241)
(378)
410*
640*
1000
-
(125*)
(195*)
(305)
540*
850
-
-
(165*)
(259)
690*
-
-
-
(210*)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
[ft (m)]
3
2
1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
5940
-
-
(1811)
4060
-
-
(1237)
3140
3860
4760
5830
(957)
(1177)
(1451)
(1777)
2530
3110
3840
4710
(771)
(948)
(1170)
(1436)
2080
2560
3160
3880
(634)
(780)
(963)
(1183)
1540
1900
2330
2860
(469)
(579)
(710)
(872)
1250
1540
1890
2310
(381)
(469)
(576)
(704)
1060
1300
1600
1960
(323)
(396)
(488)
(597)
860
1060
1310
1600
(262)
(323)
(399)
(488)
640*
790*
970
1190
(195*)
(241*)
(296)
(363)
630*
770*
-
(192*)
(235*)
(290)
660*
800*
-
(202*)
(244*)
700*
-
-
-
(214*)
-
-
-
Make sure that the portion of the total cable
which is between the service entrance and a
motor starter/controller does not exceed 25
% of the total maximum length to ensure
reliable starter operation. Single-phase
control boxes may be connected at any point
of the total cable length.
The table is based on maintaining motor
terminal voltage at 95 % of service entrance
voltage, running at maximum nameplate
amperes. In general, a voltage drop must be
maintained at 3 V/100 ft or less.
1 foot = 0.305 meter (1 meter = 3.28 feet).
0
00
000
0000
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4770
5780
7030
(1454)
(1762)
(2143)
3510
4230
5140
(1070)
(1289)
(1567)
2840
3420
4140
(866)
(1042)
(1262)
2400
2890
3500
(732)
(881)
(1067)
1970
2380
2890
(600)
(725)
(881)
1460
1770
2150
(445)
(539)
(655)
950
1160
1400
1690
(354)
(427)
(515)
990*
1190
1440
(302*)
(363)
(439)
870*
1050*
1270
(265*)
(320*)
(387)
760*
920*
1110*
-
(232*)
(280*)
(338*)
39