Tabla 6-5. READ mode, parámetros del sistema de comparación de carga RFL 9300 para dos terminales
No.
Display
...
Moving dots
0
EXIT
1
PngPng 1
3
CDC 1
5
LOC IA
6
LOC IB
7
LOC IC
8
LOC 3I0
9
REM1 IA
10
REM1 IB
11
REM1 IC
12
REM1 3I0
17
RCV ADD1
19
ALARMS
20
PH BIAS
21
GND BIAS
22
BIAS CTL
23
GND DLY
24
DLAY SEC
25
FD PHASE
26
FD GND
27
BACKUP
28
PH OC BU
29
G OC BU
30
PH TOC
31
P PICKUP
32
PH CURVE
33
PH DIAL
34
GND TOC
35
G PICKUP
36
G CURVE
37
GND DIAL
38
OVHD/UGD
39
OPEN CON
40
STUB BUS
41
CM ALM D
42
DC FILT
43
DEFAULT
44
BEEPER
45
DISPLAY
46
XMT ADD1
48
COM MODE
RFL 9300
30 de enero de 2002
B e c a u s e R F L ™ a n d H u b b e l l ® h a v e a p o l i c y o f c o n t i n u o u s p r o d u c t i mp r o v e me n t , we r e s e r v e t h e r i g h t t o c h a n g e d e s i g n s a n d s p e c i fi c a t i o n s wi t h o u t n o t i c e .
Definition
RFL 9300 is in STANDBY mode. Display controller parameter; not user-selectable.
Exit to STANDBY mode. Display function; can be set to either ENABLE or DISABLE. (1)
Value of ping-pong (round-trip delay) for remote 1.
One-way Rx delay for remote 1.
Local Phase A current.
Local Phase B current.
Local Phase C current.
Local 3I0 current.
Remote 1 Phase A current.
Remote 1 Phase B current.
Remote 1 Phase C current.
Remote 1 3I0 current.
Remote 1 Rx address. (2)
Present alarm status (four alarms).
Phase bias. Programmable; see table 6-9 for more information.
Ground bias. Programmable; see table 6-9 for more information.
Bias control. Programmable; see table 6-9 for more information.
Enable/disable ground delay. Programmable; see table 6-9 for more information.
Bias control and ground delay time (in seconds). Programmable; see table 6-9 for more information.
Local phase fault detector current. Programmable; see table 6-9 for more information.
Local ground fault detector current. Programmable; see table 6-9 for more information.
System backup functions. Programmable; see table 6-9 for more information.
Phase overcurrent backup. Programmable; see table 6-9 for more information.
Ground overcurrent backup. Programmable; see table 6-9 for more information.
Local phase time-overcurrent backup. Programmable; see table 6-9 for more information.
Local phase time-overcurrent pickup value. Programmable; see table 6-9 for more information.
Local phase time-overcurrent curve select value. Programmable; see table 6-9 for more information.
Local phase time-overcurrent dial setting value. Programmable; see table 6-9 for more information.
Local ground time-overcurrent backup. Programmable; see table 6-9 for more information.
Local ground time-overcurrent pickup value. Programmable; see table 6-9 for more information.
Local ground time-overcurrent curve select value. Programmable; see table 6-9 for more information.
Local ground time-overcurrent dial setting value. Programmable; see table 6-9 for more information.
Overhead or underground cable. Programmable; see table 6-9 for more information.
Open conductor action. Programmable; see table 6-9 for more information. (7)
Stub bus active/inactive.
Communications alarm delay. Programmable; see table 6-9 for more information.
Enable/disable dc filter. Programmable; see table 6-9 for more information.
Re-program to factory default values. Programmable; see table 6-9 for more information. (4)
Enable/disable audible beeper. Programmable; see table 6-9 for more information. (5)
Adjust display intensity. Programmable; see table 6-9 for more information. (6)
Transmit address to remote 1. Programmable; see table 6-9 for more information.
Selects hot standby communications mode. Programmable; see table 6-9 for more information.
>> La tabla continua en la próxima pagina <<
>> refiérase a la pagina 6-24 para las notas <<
6-19