M = multiples of pickup. For curve operating time (t
Curve IEC1: Standard Inverse - See Figure 6-37
t
= TD [ 0.14/(M
M
Curve IEC2: Very Inverse - See Figure 6-38
t
= TD [ 13.5/(M - 1) ]
M
Curve IEC3: Extremely Inverse - See Figure 6-39
t
= TD [ 80.0(M
M
Curve IEC4: Long Time Backup - See Figure 6-40
t
= TD [ 120.0/(M - 1) ]
M