Electrical Connection Box - Cuenod NC4 R101A Instrucciones De Montaje

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 21
Commissioning
Safety unit
Flame detection
Connector
no.
Terminal
Fan motor
Connector
no.
Terminal
Terminal
1
Earth
2
Flame detection signal
3
Live
4
Remote unlocking signal
5
Live
6
Live
7
Nozzle line preheater/release contact
8
Earth
9
Neutral
10
Live
11
Earth
12
Neutral
13
Earth
Remote
unlocking
Nozzle line preheater
Fuel oil valve
Designation
12/2008 - Art. Nr. 4200 1013 9300A
230V power supply
Malfunction signal
Igniter
Terminal
14
Fan motor live
15
Earth
16
Neutral
17
L1 on valve, electrical net side
18
Earth
19
Neutral
20
Neutral
21
Electronic igniter live
22
Earth
23
Reserved (non available)
24
Reserved (non available)
25
Fault warning light live
26
Neutral
Earth
Designation
35

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Nc6 r101aNc4 h101aNc6 h101aNc9 h101a

Tabla de contenido