8. Connection of the storage system
This chapter explains the requirements and process for connecting the storage system wiring to the unit. Read
carefully before starting the connection process.
8.1. Safety instructions for connecting the storage system
CAUTION
Before you start to make the connections, make sure there is no voltage in the inverter. Verify that the AC
protection of the auxiliary grid/genset and the DC protection of the storage system are open, as well as the PV
array and the consumption grid.
Do not switch on the power to the unit until you have successfully made the rest of the connections and the unit is
closed.
When carrying out the connections, respect the polarities marked on the electronic card. If the connection is
performed incorrectly the inverter could be damaged
Ingeteam accepts no liability for any damages caused by incorrect connection.
8.2. Wiring requirements for connecting the storage system
The wiring gauge for connecting the storage system is specified in the following table:
Wiring gauge
Wiring diameter
Wiring stripping length (L*)
L*
8.3. Use of ferrite cores
Two of the ferrite cores supplied must be used to connect the storage system. Turn each wire around twice, as
indicated in the following figure.
28
INGECON SUN STORAGE 1Play
Up to 32 A
Up to 40 A
4 mm
6 mm
2
9 ~ 13 mm
18 mm
ABH2013IQM01_C- Installation and Operation Manual
Connection of the storage system
Up to 50 A
10 mm
2
2