Ingeteam INGECON SUN STORAGE 1Play Manual De Instalacion Y Uso página 61

Ocultar thumbs Ver también para INGECON SUN STORAGE 1Play:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Display control
Battery
Setting
VBAT
Voltage (V) in the battery bank measured by the inverter.
IBAT
Current (A) in the battery bank measured by the inverter. Positive for discharge, negative
for charge.
SOC
Estimation of the lead-acid battery bank state of charge (%). For Li-Ion batteries it will
display the data received by the BMS.
STATUS
Status of the battery bank. The following states may be shown: Stand-by, Discharge,
Charge, Absorption, Flotation or Equalization.
TEMP
Battery bank temperature (ºC). In the case of the lead-acid batteries, a PT-100 sensor must
be installed.
BMS battery manager
Setting
VBAT
Voltage (V) of the Li-Ion battery.
IBAT
Current (A) of the Li-Ion battery. Negative for discharge, positive for charge.
SOC
State of charge of the Li-Ion battery (%).
I MAX CHARGE
Maximum charge current (A) of the Li-Ion battery.
I MAX DISCHARGE Maximum discharge current (A) of the Li-Ion battery.
VBAT CHARGE
Charge voltage (V) of the Li-Ion battery.
VBAT DISCHARGE
Discharge voltage (V) of the Li-Ion battery.
SOH
Health status (%) of the Li-Ion battery.
TEMPERATURE
Internal temperature (ºC) of the Li-Ion battery.
COMM STATUS
CAN communication status with the Li-Ion battery. The following states may be shown: OK
or ERROR.
Photovoltaic
Setting
Voltage (V) of the PV array. If the PV array is not available but the inverter has started, the
VDC
voltage (V) of the internal DC bus is displayed.
IDC
Current (A) of the PV array.
PDC
Power (W) of the PV array.
Inverter
Setting
VAC
Voltage generated by the inverter (V).
IAC
Current through the inverter (A).
FAC
Frequency generated by the inverter (Hz).
PAC
Active power through the inverter (W).
STATUS
Inverter status. The following states may be shown: Disconnected, Connected, or Waiting
the connection with the grid/genset (waiting time according to selected regulations).
Grid
Setting
VAC
Auxiliary grid/genset voltage (V).
IAC
Auxiliary grid/genset current (A).
ABH2013IQM01_C - Installation and Operation Manual
Explanation
Explanation
Explanation
Explanation
Explanation
Ingeteam
EN
ES
FR
PT
61

Publicidad

Tabla de contenido

Solución de problemas