SMA Solar Technology America LLC
11. Configure the energy meter for operation with the
inverter. When doing so, set the DIP switches 7 and
8 to ON (1) and the DIP switches 1 through 6 to 0.
This ensures that the energy meter data can be
transmitted to the inverter.
6.6
Connecting the Switch and Outlet for Secure Power
Supply Operation
Requirements:
☐ The technical requirements must be met for connecting the switch and outlet for secure power
supply operation (see Section 10 "Technical Data", page 63).
☐ All electrical installations must be carried out in accordance with the local standards and the
National Electrical Code
Additionally required material (not included in the scope of delivery):
☐ One standard outlet
☐ One standard switch (e.g. light switch)
☐ Conduits (trade size: 21 mm (0.75 in) or smaller with suitable reducer bush)
☐ Listed rain-tight or conduit fittings for wet locations (trade size: 21 mm (0.75 in) or smaller with
suitable reducing bush)
Procedure:
• Connect the outlet for secure power supply operation.
• Connect the switch for secure power supply operation.
Connect the outlet for secure power supply operation
Requirements on・the conductors:
☐ The conductors with regards to its ampacity, rated temperatures, operating conditions and its
power loss must be made in accordance with the local standards and the National Electrical
®
Code
ANSI/NFPA 70 or the Canadian Electrical Code
☐ Conductor type: copper wire
☐ The conductors must be made of solid wire, stranded wire or fine stranded wire. When using
fine stranded wire, bootlace ferrules must be used.
☐ Conductor cross-section: 2.5 mm² to 4 mm² (14 AWG to 12 AWG)
Installation Manual
®
ANSI/NFPA 70 or the Canadian Electrical Code
6 Electrical Connection
0
N
®
CSA C22.1.
®
CSA C22.1.
SBSxx-US-10-IA-xx-11
41