Replace Battery - KPS -PA70 Manual De Funcionamiento

Pinza amperimétrica digital
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

meter shows and keeps the surge current value.
• Read the current surge value on the LCD display.
Nota:
1) Clamping two or more leads of circuit to be tested simultaneously will not get
the correct measuring results.
2) To get accurate reading, connect the lead to be tested at the center of cur-
rent clamp.
3) If, in the manual measuring range mode, the LCD shows "OL", which indi-
cates overrange, choose a higher measuring range.
4) In the manual measuring range mode, if you don't know the value to be
measured in advance, choose the highest measuring range.
5) "
" means that maximum input current is 1000A AC (RMS).
4.18 NCV Measurement
1) Turn the meter to NCV mode.
2) Place the meter top close to the conductor. When test voltage is greater than
110 Vac (RMS), when the meter is close to the conductor, the meter induction
voltage indicator will turn on and the buzzer will give an alternating high-low
alarm sound.
Note:
1) Even there is no indication, voltage may exist still. Don't use non-contact
voltage detector to judge whether there is voltage in the wire. Detection opera-
tion could be affected by socket design, insulation thickness, type and other
factors.
2) When inputting voltage on the meter input terminal, due to the existence of
the induced voltage, voltage induction indicator also may light.
3) External sources of interference (such as flashlight, motor, etc.) may incor-
rectly trigger non-contact voltage detection..
5.
MAINTENANCE

5.1 Replace Battery

Before opening the meter battery cover, remove probe from the circuit
to be measured to avoid electric shock.
KPS-PA70 • Digital clamp meter
WARNING
46

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

602150001

Tabla de contenido