Error
E534
Writing error of approach torque
E536
Writing error of the error table
E666
Error in the linearity table
E667
Error seeking zero position
E668
Error
seeking
according to speed
Locking codes
Codes
0 1
Programming disabled
0 2
Loosening disabled
0 3
Lock on batch count NcyOK
0 4
Lock on NOK
0 5
Tool disabled
0 6
Lock on External start cycle only
EAP/EDP
Description
This error can only appear at the end of the first phase of the engine
tuning. It could be an engine problem, it could be a magnet problem in
the engine shaft extension, the power module or the DSP board. Contact
our customer service.
This error can only appear after the second phase of the engine tuning.
This can be a problem with the magnet in the engine shaft extension, or a
problem on the hall board. Contact our customer service.
offset
evolution
This error can only appear at the end of the third phase of the engine
tuning. This can be a problem with the magnet in the engine shaft
extension, or a problem on the hall board. Contact our customer service.
Description
Programming is disabled with the PDA (The box "Programming
authorisation" of Station menu \ General parameters", is not validated).
The loosening direction is disabled with the PDA (The box "Run reverse
authorisation" of Station menu \ General parameters", is not validated).
When the tool is connected to a DTU, apply +24V signal on the
REVERSE VALIDATION input to enable the operator to loosen.
The box function "Lock on batch count NcyOK" is validated in the PDA,
Station menu \ DTU parameters. The tool is locked when the number of
cycles reaches the number of NcyOK programmed (see cycle screen of
the PDA). Apply a +24V signal on the RESET input of the DTU to
unlock the tool.
The box function "Lock on NOK" is validated in the PDA, Station menu
\ DTU parameters. The tool is locked when a reject tightening report
appears. Apply a +24V signal on the REJECT ACKNOWLEDGE input
of the DTU to acknowledge the default.
The tool is locked by the SPINDLE ENABLED input of the DTU. Apply
24V to enable the tool to work.
The tool is locked by "External start cycle only" meaning the tool
triggers are not activated. To enable the tool triggers, with the PDA
(Station menu / DTU parameters) unselect "External start cycle only".
Part no
Issue no
Language English
Date
Page
Checking/Actions
Checking/Actions
6159936431
06
09/2009
24
19 /