Service
4 Service
4.1 Troubleshooting
This guide provides tables showing messages appearing in
the inverter display, known as events. The tables contain
descriptions as well as which actions to take, when an
event arises. For the full event list, refer to the FLX Series
User Guide.
To view events, go to the Log menu and enter the
Eventlog menu. The latest event registered by the inverter,
as well as a list of the 20 most recent events, is shown
Event Type
-
ID
Status message Description
201 Tpower_high.
The internal temperature of the
inverter is too high.
Table 4.1 How to Read the Event Tables
Event Type
Indicates whether the event relates to grid, PV, internal or fail safe issues.
ID
The specific event ID.
Display
Text shown in display.
Description
Description of the event.
Action
Description of which action to take prior to contacting any other parties.
If the prescribed action has not identified the malfunction, contact the DNO for further assistance.
DNO
Hotline
If the prescribed action has not identified the malfunction, contact the inverter hotline for further assistance.
PV
If the prescribed action has not identified the malfunction, contact the PV supplier for further assistance.
Grid-related Events
ID
Status
Description
message
1–6
Grid voltage too low.
7–9
Grid voltage average over 10
minutes too high.
10–15
Grid voltage too high.
16–18
The inverter has detected a
voltage peak on the grid.
19–24
Grid frequency too low or too
high.
25–27
Loss of mains, Phase-to-phase
voltages too low.
28–30
Loss of mains, ROCOF out of
range.
31–33
DC grid current too high.
here. When the inverter enters the On grid mode, the most
recent event is cleared and is shown as 0.
The event code is made up of 2 elements: the group
classifier and the event ID. The group classifier describes
the general type of the event, while the event ID is used
to identify the specific event.
Table 4.1 is an overview of how the tables of inverter
events are constructed and how to use them.
Action
Check the inverter is not covered and that the
ventilation duct is not blocked. If not, call installer.
Action
Call the installer and inform about the grid-phase voltage.
Check voltage and AC installation, if the voltage is zero
check the fuses.
Call the installer and inform about the grid-phase voltage.
Check that the installation is correct according to the instal-
lation guide. If so, then increase the mean voltage limit
according to section Functional Safety.
Call the installer and inform about the grid-phase voltage.
Check voltage and AC installation.
Call the installer and inform about the grid frequency..
Call the installer and inform about the voltage on all three
phases.
Check the phase-to-phase voltages and the AC installation.
If the event reoccurs several times each day, contact the
DNO.
For occurrence several times daily, contact installer.
Installer: Perform on-site grid analysis.
L00410568-03_2q / Rev. date: 2014-06-20
4
DNO Hotline PV
-
x
-
DNO Hotline PV
x
-
-
x
-
-
x
-
-
x
-
-
x
-
-
x
-
-
x
-
-
-
x
-
33
4