No.
Description
5.4.1.0
In2 active/inactive
5.4.2.0
In2 (value range)
5.5.0.0
PID parameter
5.5.1.0
P parameter
5.5.2.0
I parameter
5.5.3.0
D parameter
5.6.0.0
Error
5.6.1.0
HV/AC
5.6.2.0
Emergency opera-
tion speed
5.6.3.0
Auto reset time
5.7.0.0
Other settings
5.7.1.0
Display orientation
5.7.2.0
Pressure value cor-
rection
5.7.6.0
SBM function
Installation and operating instructions SIE - DIE
Type
Symbol Values/explanations
±
ON
External setpoint input 2 active
OFF
External setpoint input 2 inac-
tive
±
Setting of the value range
Possible values: 0..10 V/2..10 V/
0..20 mA/4..20 mA
Settings for PID control
±
Setting of the proportional part
of the control
±
Setting of the integrating part of
the control
±
Setting of the differentiating
part of the control
Settings for behaviour in case of
error
±
HV "Heating" operating mode
AC "Cooling/air-conditioning"
operating mode:
Display of emergency operation
speed
±
Time until automatic acknowl-
edgement of an error
±
Display orientation
Display orientation
±
When the pressure value correc-
tion is active, the differential
pressure between two defined
measuring points (generally on
the pump flange) will be consist-
ently kept to a current setpoint
by changing the speed of the
pump.
Pressure value correction off
Pressure value correction on
±
Setting for behaviour of signals
SBM run signal
SBM readiness signal
SBM mains on signal
English
Display conditions
Is not displayed when
2 = inactive
Incl. all submenus; is only
displayed when PID control
is active
Is only displayed in
(p-c mode
71