CONFIGURATION

pq
Using
we can change the values and push
up the configuration process.Whenever we want to quit the configuration sequence press
point.
0
P. LINE
SET P
00,0 bar
00,0 bar
1
SET UP MENU
2
LANGUAGE
ENGLISH
3
MAX. INT. PUMP
OFF
4
ROTATION SENSE
0
0 Hz
5
MIN. SPEED
15 Hz
6
LEVEL PROBE
NO
7
PROGRAMMING MENU
8
SET PRESSURE
02,0 bar
9
DIF. START
0,3 bar
10
TIMER STOP
5 s
11
VIEW MODE
NORMAL
12
SERIAL CONTROL
SLAVE
13
DIRECTION
CH: 1
14
LINE
SET P
00,0 bar
00,0 bar
In case of group assembly, after pressing AUTOMATIC in the MASTER device, the AUTOMATIC LED LIGHT of the SLAVE device
will start to flash intermittently, indicating that communication between both devices is ready. If this does not happen verify the
connection (fig 7).
ENTER
for validation. After every
To start configuration sequence push
Being inside configuration menu we are having access to the phase of installation.
pq
By mean of keys
we can choose the languages: "LANGUAGE ENGLISH", "LANGUE
FRANÇAISE", "LINGUA ITALIANA" and "IDIOMA ESPAÑOL".
pq
By mean of keys
input the nominal current intensity value in A of the pump, enabling the
thermal protection. This value is located over the characteristics plate of the motor. Press
for validation. (Is recommended to enter a current vaule 15% higher than the nominal value).
By mean of the
START/STOP
(0/1) it can be changed. Press ENTER for validation.
pq
By mean of keys
we can increase the lower limit of the speed of rotation of the pump´s
motor.
If the installation does not have level probe press
If the installation has a level probe, use keys
Being inside configuration menu we are having access to the phase of programmation.
This will be the system operating pressure. Use keys
WARNING ! The input pressure must be al least 1 bar lower than the maximum pressure of
the pumps.
NOTE
: In case of group assembly, all the system operates at the pressure set in the MASTER device,
so that the configuration of set pressure in the slave device is superfluous.
The default value is 0,6 bar. This value of pressure is substracted to the system setpoint, resulting
the final pressure to which the system will set in motion the pump when the hydraulic network has
pq
a demand. Use keys
to modify the initial value. It is recommended to maintain this value
between 0,3 and 0,6 bar. Example:
n
Input pressure: 2 bar.
n
Differential start: 0,3 bar
n
Final start pressure: 2 - 0
TIMER STOP default value is 5". This will be the employed time by the system in stopping once
ceased the consumption in all the installation. Using keys
There are 2 view modes to choose:
n
NORMAL
: it is visualized "P LINE" (real pressure of the installation) and "INPUT P" (configured
pressure).
n
SERVICE
: it is visualized "Hz" (working frequency of the inverter), "SET" (configured pressure),
"P.LINE" (real pressure of the installation) y "FL" (flow sensor state).
The SPEEDMATIC is configured by default as "SLAVE".
n
In case of individual assembly just confirm "SLAVE" by pushing
n
In case of group assembly (M-S), we will do the same for the slave device. For the
"MASTER" device we will change "SLAVE" by "MASTER" pushing
n
In case of assembly of more than 2 devices, we will change "SLAVE" by "SWITCHER"
q
pushing
twice - see instructions of our station
It allows to set the communication channel whe the sation
ENTER
.
After pressing
ENTER
pushbutton, the system will remain configured showing the type of view
chosen in the previous section 11. Press
In case of group assembly press
ENTER
are sequenced the successive messages that make
MENU
MENU
during 3".
push-button is v
erified the rotation sense. By mean of keys
ENTER
to validate NO.
pq
to change NO by YES.
pq
,6 = 1,4 bar.
SPEEDCENTER.
AUTOMATIC
in order to quit manual mode.
AUTOMATIC
only in the device configured as MASTER.
-11-
being saved the modified parameters untill this
to modify the initial value (2 bar).
pq
we can modify the initial value.
ENTER
.
q
.
SPEEDCENTER
is connected. Push
MENU
MENU
3"
3"
ENTER
ENTER
MENU
ENTER
MENU
ENTER
pq
MENU
ENTER
ENTER
MENU
ENTER
MENU
MENU
ENTER
ENTER
MENU
ENTER
MENU
MENU
ENTER
ENTER
MENU
ENTER
MENU
ENTER
MENU
ON
OFF

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Speedmatic 1314 masterSpeedmatic 1307Speedmatic 1307 master

Tabla de contenido