Event message
Isolation error
No branding
No connection to the
energy meter
L and N swapped
Country parameters
invalid
Power reduction due to
temperature
Reading CountryCode
failed
Fan faulty
Grid frequency too high
for reactivation
Grid frequency too low
for reactivation
0020273427_02 VPV I Installation and maintenance instructions
Symbol
Cause
The insulation resistance between the plus
and minus input and earth exceeds the
permissible value.
For safety reasons, the inverter must not
feed into the network.
The inverter has incorrect unit data or unit
data is missing.
The inverter therefore cannot feed into the
network.
There is no communication connection
between the inverter and the energy meter,
or the communication connection between
these is incorrect.
Outer and neutral conductors are inverted.
For safety reasons, the inverter must not
feed into the network.
The inverter cannot feed into the network be-
cause it does not have any valid parameters.
The maximum permissible temperature has
been reached.
The inverter could not correctly read the set
country from the cylinder.
The inverter's internal fan is defective.
The inverter may feed into the network with
reduced power.
After switching off, the inverter cannot con-
tinue to feed in because the mains frequency
exceeds the statutory activation value.
After switching off, the inverter cannot con-
tinue to feed in because the mains frequency
falls below the statutory activation value.
Appendix
Measure
See measures on Residual current too
high.
If the message occurs more than five times a
day, contact customer service.
Ensure that the connection to the energy
meter is correct.
Ensure that the correct energy meter
is selected in menu item Main menu
→ Settings → Energy management →
Configuration.
Check the contact assignment in the
alternating current plug.
Check the alternating current installation
(utility connection).
If the message occurs more than five times,
contact customer service.
Check whether the installation conditions
have been complied with.
Checking the country setting
Disconnect the inverter from the direct
current and alternating current power
supply. Carry out a restart.
Request the password for the service
code. Delete the country setting. Set the
country setting again.
If the message occurs more than five times,
contact customer service.
Ensure that the correct country setting
has been set.
If required, inform the local energy sup-
plier.
If required, have the local energy sup-
plier check the network conditions up
until the photovoltaic installation's net-
work interconnection point.
Carry out a network analysis directly at
the feed-in point of the inverter(s). Carry
out a network analysis at the network in-
terconnection point. If required, inform
the local energy supplier about the res-
ults of the tests.
In consultation with the energy supplier,
adjust the threshold values for mains
voltage and/or mains frequency, if re-
quired. To make adjustments, you re-
quire an access code (from the code
generator). Contact Customer Service for
this.
Have the local energy supplier ensure
that the relevant specification for the
mains voltage and mains frequency is
complied with.
See measures on Grid frequency too high
for reactivation.
45