Wiring - Balluff BTL5-A-M-J-DEXA Serie Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

BTL5-A/C/E/G1_-M_ _ _ _-J-DEXA/B-K_ _
Micropulse Linear Transducer - Rod Style
4

Wiring

Important wiring note:
Note that the displace-
ment measuring system
must be connected to the
potential compensation system in
accordance with the specifica-
tions of DIN EN 60079-14. The
external connection for the
transducer is accomplished by
means of metallic conducting
installation in a grounded area.
The flange and housing are me-
chanically fixed together and
electrically identical, so that no
potential differences between
them can occur.
If no metallic conducting instal-
lation location can be assured,
the housing must be grounded
using the ground screw on the
cover.
The system and the control cabi-
net must be at the same ground
potential. A sufficient potential
compensation has to be
provided such that it does not
flow through the cable shield!
To ensure electromagnetic com-
patibility (EMC), which Balluff
verifies by the CE Marking, the
following points must be strictly
observed.
BTL transducer and processor /
controller must be connected
using shielded cable.
Shield: Copper-stranded mesh,
85 % coverage. The shield is
connected to the housing of the
transducer. It must be grounded
on the control side.
Unused leads can be tied to
GND on the control side, but
they must never be connected to
the shield.
Refer to ➥ ➥ ➥ ➥ ➥ table 4-1 for wiring
assignments.
The installed cable fitting
was tested with reduced
tensile force in accor-
dance with EN 60079-0.
This is why the connection cable
must be routed in a permanent
location and protected against
tension and rotary loads using an
additional clamp. It may not be
used with drag chains.
8
english
Output signals
Wire color
BTL5-A11
YE yellow
not used
PK pink
10...0 V
GN green
0...10 V
GY grey
Supply voltage (external)
Wire color
BTL5-A/C/E/G1
BU blue
GND
BN brown
+24 V
WH white
not used
Table 4-1: Wiring
when mounted
Fig. 4-1: GND screw for 4 mm
nominal cross section
Potential compensation
as per DIN EN 60079-14
Fig. 4-2: BTL5-C/E...K... with processor/controller, wiring example
When routing the cable between the
transducer, controller and power
supply, avoid proximity to high volt-
age lines to prevent noise coupling.
Especially critical is inductive noise
caused by AC harmonics (e.g. from
phase-control devices), against
which the cable shield provides only
limited protection.
Length of signal transmission max.
20 m. Longer lengths may be used if
construction, shielding and routing
are such that external noise fields
will have no effect on signal integrity.
Flameproof enclosure
...-C10
...-C17
...-E10
0...20 mA 20...0 mA 4...20 mA 20...4 mA not used
10...0 V
10...0 V
10...0 V
0...10 V
0...10 V
0...10 V
0 V
Caution:
In addition to the grey 0 V wire
only one of the output signals
may be connected, i.e. either the
yellow, pink, or green wire!
Note:
Due to the seperate output
drivers a small voltage difference
(i.e. a constant offset of <10 mV)
appears between these two out-
put signals.
Reference GND for supply
voltage and EMC!
2
YE
GY
PK
GN
BN
BU
WH
Ignition Class "d"
...-E17
...-G11
10...0 V
10...–10 V
0...10 V
–10...10 V