salmson LRE Serie Manual De Instalación Y Puesta En Servicio página 81

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

8.6.6 Activating/deactivating service
mode
8.6.7 Activating/deactivating access
disable
Installation and operating instructions LRE-JRE
Additional settings can be made in service mode. The mode is acti-
vated or deactivated as follows.
Caution - material damage!
Improper setting changes can lead to pump operation errors, which
can lead to material damage to the pump or system.
• Settings in service mode should only be made during commission-
ing and only by qualified personnel.
ON
• Set DIP switch 1 to the ON position.
Service mode is activated. The symbol shown here flashes on the sta-
1
tus page.
The sub-elements of menu 5.0.0.0 switch from the "Information"
element type to the "Selection/setting" element type, and the stand-
ard "access disable" symbol (see symbol) is hidden for the respective
elements (except for <5.3.1.0>).
The values and settings for these elements can now be edited.
In order to prevent impermissible changes to the pump settings, all
functions can be disabled.
When access is disabled, this is shown on the status page by the
default "access disable" symbol.
To activate or deactivate this, proceed as follows:
ON
• Set DIP switch 2 to the ON position.
Menu <7.0.0.0> is displayed.
2
• Turn the white button to activate or deactivate the disable.
The current state of the disable is represented on the symbol display
by the symbols shown here.
• To confirm the change, press the white button.
The new setpoint will be accepted and the display will return to the
status page.
Disable active
No changes can be made to setpoints or settings. The read access to
all menu elements remains as it was.
Disable inactive
The elements of the basic menu can be edited (menu elements
<1.0.0.0>, <2.0.0.0> and <3.0.0.0>).
NOTE
To edit the sub-elements of menu <5.0.0.0>, service mode must also
be activated.
ON
• Reset DIP switch 2 to the OFF position.
The display returns to the status page.
2
NOTE
Errors can be acknowledged after a waiting period despite the "access
disable" being active.
English
74

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Jre serie

Tabla de contenido