4.3

Technical data

Model
Delivery
(1)
Thermal power
(1)
Fuel
Operation
Use
Ambient temperature
Combustion air temperature
Pump
Noise levels
Sound pressure
(2)
Sound power
Burner weight
Reference conditions: Ambient temperature 20°C - Barometric pressure 1013 mbar -Altitude 0m a.s.l. (H i = 11.86 kWh/kg)
(1)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum output. The sound power
(2)
is measured with the "Free Field" method, as per EN 15036, and according to an accurate "Accuracy: Category 3" measurement, as described in
EN ISO 3746.
4.4

Electrical data

Model
Electrical supply
Motor
Capacitor
Ignition transformer
Absorbed electric power
Protection level
4.5

Burner equipment

Flange with insulating gasket ............................................. No. 1
Screw and nuts for flange .................................................. No. 1
Remote reset connection ................................................... No. 1
Screws and nuts for fixing the flange to the boiler ............. No. 4
Recirculating pipe ............................................................... No. 1
Flexible hoses with nipples ................................................ No. 2
7 pin plug ............................................................................ No. 1
Installer booklet ................................................................... No. 1
Spare Parts List................................................................... No. 1
Remote reset kit
The burner has a remote reset kit (RS) consisting of a con-
nection and a push-button operating at a distance of 20
metres max.
In order to install it, remove the safety lockout device installed
at the factory and insert the lockout supplied with the burner
(see electrical
diagram).
20136520

Technical description of the burner

BGK1
1.5 3.0
kg/h
17.8 35.6
kW
°C
°C max
bar
62
dB (A)
73
kg
13
BGK1
A
rpm
rad/s
F
4
kW
0.25
8
GB
BGK2
2.7 5.0
32 59.3

Light oil, viscosity 4
6 mm
Intermittent (FS1)
Boilers: water and diathermic oil
0 - 40
40
Pressure: 8
15
63
74
13
BGK2
Single-phase, ~ 50Hz 230V ± 10%
0.8
2750
288
4
Secondary 18 kV - 25 mA
0.27
IP 40
BGK3
3.8 6.15
45.0 73.0
2
/s at 20°C
62
73
16.5
Tab. B
BGK3
1.8
2800
294
8
0.46
Tab. C

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Bgk2Bgk337370063737066373745620012189