baltur BT 40 DSN 4T Manual De Instrucciones página 19

Quemadores de aceite combustible de dos etapas
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

HYDRAULIC SCHEMATIC DIAGRAM FOR TWO-FLAME OR MODULATING BURNERS WITH FUEL OIL (MAX.
15° E AT 50° C)
Note Fuel recovery tanks (diameter ~ 150 mm - height ~ 400
mm) must be installed as close as possible to the burner
at least 0.5 m above the burner pump.
1
MAIN TANK
2
FILTER
3
CIRCULATION PUMP
4
WATER AND SYSTEM OUTLET
5
AIR/GAS OUTLET - NORMALLY CLOSED
6
FUEL RECOVERY TANK AND DEGASSER
7
NON-RETURN VALVE
8
BY-PASS (NORMALLY CLOSED)
9
PRESSURE REGULATOR ADJUSTABLE BETWEEN 0.5-2
BAR
10
PRESSURE GAUGE (0-4 BAR)
11
STEAM OR HOT WATER FUEL OIL HEATING COIL
HEATING ELECTRIC CABLE (IF NECESSARY)
17 / 40
0006081310_201211

Publicidad

Tabla de contenido
loading

Tabla de contenido