15
ELECTRICAL CONNECTIONS
The automation is designed to be powered by the mains supply at 230V AC
50 Hz.
Therefore, connect the automation to the mains through a double insulated
3x2.5 mm² cable, making it pass through a submerged pipe prepared during
the installation of the KT230 foundation plate (see Fig.3).
Once inside the cabinet, the cable must continue upward on the left side of
the automation; insert it through the rubber cable gland to the left of the
box and connect it to the terminal block with a fuse, as shown in Fig. 22.
Ensure the cable so that it does not suffer damage during the movement of
the mechanical parts inside the cabinet.
15.1) Type of connection cables and minimum thicknesses
CONNECTION
230V Power supply
Photocell transmitters
Photocell receivers
24V accessory power
Safety and control devices
Antenna Connection
16
INSTALLATION OF A SYSTEM TYPE
Here we list the components needed for installation of a system type of an Agilik 4 or Agilik 6 series automation.
11
1) Automatic Barrier Agilik 4 or Agilik 6 Series.
2) integrated control unit.
3) Flashing lights.
4) External Photocell
5) Bar with shockproof rubber and LED strip.
6) Reflective sticker.
9) Internal Photocell
10) Fixed support for bar.
11) Key or keypad release switch
26
CABLE TYPE
OUTDOOR CABLES FOR
UNDERGROUND INSTALLATION
CEI EN 50267-2-1
RG58
4
22
CABLE LENGTH
1 - 10 m
3 x 2.5 mm²
2 x 0.5 mm²
4 x 0.5 mm²
2 x 0.5 mm²
2 x 0.5 mm²
10
9
8
7
6
L
N
CABLE LENGTH
CABLE LENGTH
10 - 20 m
3 x 2.5 mm²
2 x 0.5 mm²
2 x 0.5 mm²
4 x 0.5 mm²
4 x 0.5 mm²
2 x 0.5 mm²
2 x 0.5 mm²
2 x 0.5 mm²
MAX 10 m
5
4
3
2
20 - 30 m
3 x 4 mm²
2 x 1 mm²
1